13 Accessories
A. Gas Log/Lighter Provision
WARNING! Fire and/or Asphyxiation Risk! Use with solid wood fuel or decorative gas appliance only. Gas fire gener- ates fumes.
•DO NOT install unvented gas logs
•Damper must be locked fully open when gas logs are installed
A certified gas log lighter or decorative gas log set can be installed in this fireplace.
• Maximum input is 150,000 BTU/hr. |
• Decorative gas appliance must be certified to ANSI Z21.60 |
“Standard for Decorative Gas Appliances for Installation |
in Vented Fireplaces”. |
• Must be installed in accordance with the National Fuel |
Gas Code, ANSI Z223.1. |
• A gas log set must incorporate a gas shutoff. |
• Gas log set requires the damper to be locked fully open. |
• Knockouts are provided on both sides of the fireplace for |
1/2 in. (13 mm) iron pipe. |
• A locating dimple is located on both sides of the fireplace in |
the molded brick panel for drilling a 1 in. (25 mm) diameter |
hole for installation of a gas line. After the panel is installed, |
Firebox
Refractory
Seal with fireplace mortar or
Gas Line
Repack
Insulation
Knockout
Outer Shell
of Fireplace
Maintain air clearance to combustibles.
Combustible
Materials
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| (38 mm) |
|
|
|
|
|
|
|
|
|
|
| |
|
|
| Gas Line |
|
|
|
|
| air space | ||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| Combustible materials | |||||
|
|
|
|
|
| ||||||
|
|
|
|
|
| ||||||
|
|
|
|
|
| may be located at zero | |||||
|
|
|
|
|
| ||||||
|
|
|
|
|
| clearance to gas line | |||||
|
|
|
|
|
| ||||||
|
|
|
|
|
| beyond 4 in. (102 mm) | |||||
|
|
| 4 in. |
|
| from fireplace side. | |||||
|
|
|
|
| |||||||
| (102 mm) |
|
|
|
|
|
|
drill the hole for the gas line. |
• Seal panel around pipe with fireplace mortar or a non- |
combustible sealant. |
Figure 13.1 Gas Line Installation
B. Wood Burning Inserts
WARNING! Risk of Fire! Improper installation of wood inserts may cause fireplace or chimney system to overheat.
If a wood burning insert is being installed in this fireplace, Hearth & Home Technologies recommends full reline of the chimney.
•Cooling air openings at the top of the chimney must not be obstructed in any manner.
•Hearth & Home Technologies recommends securing the reline at the top of the flue and using the cap certified for use with this fireplace system.
44 | Heat & Glo • |