E. Combustible Mantel
•See Figure 12.11.
•A combustible mantel may be positioned no lower than 22 in. (508 mm) above the top of the fireplace opening.
•A combustible mantel may have a maximum depth of 12 in. (305 mm).
•Combustible trim and mantels cannot be placed within 6 in. (152 mm) of the fireplace opening (top or sides).
•Combustible materials projecting more than
•Combustible trim must not cover the metal surfaces of the fireplace.
•Mantel clearance is in accordance with Section
7 ft (2134 mm)
minimum
floor to ceiling
Combustible Wall Noncombustible Decorative Facing
2 x 4 stud header |
|
|
| 12 in./305 mm MAXIMUM |
| ||
|
| ||||||
Standoffs |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
|
|
|
| 22 in./559 mm MINIMUM |
Measured from top of fireplace opening
Seal joint with
Figure 12.11 Clearances to Mantels or other Combustibles above Fireplace
42 | Heat & Glo • |