After entering the correct password, a display similar to the following will appear:
I | N | I | T |
| Z | O | N | E |
| # | 1 |
|
|
|
|
E | N | A | B | L | E | D |
|
|
|
|
|
|
|
|
|
Zone Disabled/Enabled
This display allows the user to ENABLE or DISABLE Initiating zones. This display window shows that initiating ZONE #1 is enabled. To toggle from ENABLED to DISABLED or visa versa, press the SELECT button.
SET
SELECT
FUNCTION
After selecting ENABLED or DISABLED, press the SET button to set and move to the next zone.
Press the SELECT button to toggle between ENABLED or DISABLED.
To skip to the next function, press the bottom button.
After selecting all four zones or pressing the FUNCTION (bottom) button, the following will appear in the display window:
O | U | T | P | U | T |
| # | 1 |
|
|
|
|
|
|
|
E | N | A | B | L | E | D |
|
|
|
|
|
|
|
|
|
Output Enable/Disable
This display allows the user to ENABLE or DISABLE any of the output circuits.
SET
SELECT
FUNCTION
After selecting ENABLED or DISABLED, press the SET button to set and move to the next output.
Press the SELECT button to toggle between ENABLED or DISABLED.
To skip to the next function, press the bottom button.
After selecting all four outputs or pressing the FUNCTION (bottom) button, the following will appear in the display window:
Disabling any input or outputs will create a trouble condition on the panel.
Disabling a releasing circuit will create a supervisory condition.
S | Y | S | T | E | M |
| M | O | D | E | : |
|
|
|
|
N | O | R | M | A | L |
|
|
|
|
|
|
|
|
|
|
16