To Silence A Signaling Appliance

VFR-400 • 5403548 • REV D • 10/07

To Silence A Signaling Appliance

Press the SIGNAL SILENCE button. All silencable outputs will de-activate. A trouble condition will be created and the amber Alarm Silenced LED will light.

Where audible and/or visual indicators are being used as an evacuation signal, do not silence an alarm condition without investigating and determining that an emergency condition does not exist.

Notes: 1) Alarms initiated from zones that are in the waterflow mode cannot be silenced. The panel must be reset to silence audible alarm devices.

2)If silenceable waterflow indication is desired it must be programmed as conventional alarm and annunciated on the zone identification portion of the LCD.

To Reset an Alarm or Supervisory Condition

1)Determine the cause of the alarm condition and if necessary remove the cause.

2)Press the reset button.

To Reset A Trouble Condition

1)Determine the cause of the trouble condition and remove the cause.

2)This circuit is self-restoring. When all trouble conditions are removed all indications will return to normal.

Note: When an initiating device zone is operated in a Class A (Style D) mode any trouble condition will require manual operation of the reset switch to restore the panel to normal after the fault has been corrected.

Lamp Test

When the panel is in a Normal Condition, pushing the top two buttons will illuminate all of the LED's and display for approximately one second.

Remote Annunciator Model RA-4410RC Operation

Red LED’s:

Initiating Device Circuits Active (4)

 

Notification/Release Circuits Active (4)

 

Common Alarm (1)

Green LED’s:

AC Power

Yellow LED’s:

Initiating Device Circuits troubles (4)

 

Output Circuit Troubles (4)

 

supervisory Bell Output Active (4)

(1)each: Supervisory Zone, Power Trouble, Supervisory Trouble, System Trouble, Ground Fault, Discharging/Discharged, Alarm Silenced RA-4410RC

ZONE 1

OUTPUT 1

ZONE 2

OUTPUT 2

ZONE 3

OUTPUT 3

ZONE 4

OUTPUT 4

AC POWER

SUPERVISORY 1

POWER TBL

SUPERVISORY 2

SYSTEM TBL

LAMP TEST

COMMON ALARM

SUP TBL

ALARM SILENCE

GROUND FAULT

STEADY: DISCHARGE

 

FLASHING: PRE-DISCHARGE

DWG# 3550-17VKG

Basic Operation

The appropriate LED flashes to indicate a change of status on the panel. A trouble or supervisory condition will flash the appropriate Yellow LED indicating the location of the condition. If any outputs are programmed as TROUBLE or SUPERVISORY BELL, that Yellow output LED will flash indicating the output is activated. Pressing the BUZZER SILENCE button on the panel changes the flashing zone Amber LED to steady on and turns the flashing Yellow output LED off.

An alarm or low air alarm condition will flash a Red LED indicating the zone in alarm and any outputs mapped to that zone that

12

Page 12
Image 12
Viking VFR-400 To Silence A Signaling Appliance, To Reset an Alarm or Supervisory Condition, To Reset A Trouble Condition