To Silence A Signaling Appliance
Press the SIGNAL SILENCE button. All silencable outputs will
Where audible and/or visual indicators are being used as an evacuation signal, do not silence an alarm condition without investigating and determining that an emergency condition does not exist.
Notes: 1) Alarms initiated from zones that are in the waterflow mode cannot be silenced. The panel must be reset to silence audible alarm devices.
2)If silenceable waterflow indication is desired it must be programmed as conventional alarm and annunciated on the zone identification portion of the LCD.
To Reset an Alarm or Supervisory Condition
1)Determine the cause of the alarm condition and if necessary remove the cause.
2)Press the reset button.
To Reset A Trouble Condition
1)Determine the cause of the trouble condition and remove the cause.
2)This circuit is
Note: When an initiating device zone is operated in a Class A (Style D) mode any trouble condition will require manual operation of the reset switch to restore the panel to normal after the fault has been corrected.
Lamp Test
When the panel is in a Normal Condition, pushing the top two buttons will illuminate all of the LED's and display for approximately one second.
Remote Annunciator Model RA-4410RC Operation
Red LED’s: | Initiating Device Circuits Active (4) |
| Notification/Release Circuits Active (4) |
| Common Alarm (1) |
Green LED’s: | AC Power |
Yellow LED’s: | Initiating Device Circuits troubles (4) |
| Output Circuit Troubles (4) |
| supervisory Bell Output Active (4) |
(1)each: Supervisory Zone, Power Trouble, Supervisory Trouble, System Trouble, Ground Fault, Discharging/Discharged, Alarm Silenced
ZONE 1 | OUTPUT 1 |
ZONE 2 | OUTPUT 2 |
ZONE 3 | OUTPUT 3 |
ZONE 4 | OUTPUT 4 |
AC POWER | SUPERVISORY 1 |
POWER TBL | SUPERVISORY 2 |
SYSTEM TBL | LAMP TEST |
COMMON ALARM | |
SUP TBL | ALARM SILENCE |
GROUND FAULT | STEADY: DISCHARGE |
| FLASHING: |
DWG#
Basic Operation
The appropriate LED flashes to indicate a change of status on the panel. A trouble or supervisory condition will flash the appropriate Yellow LED indicating the location of the condition. If any outputs are programmed as TROUBLE or SUPERVISORY BELL, that Yellow output LED will flash indicating the output is activated. Pressing the BUZZER SILENCE button on the panel changes the flashing zone Amber LED to steady on and turns the flashing Yellow output LED off.
An alarm or low air alarm condition will flash a Red LED indicating the zone in alarm and any outputs mapped to that zone that
12