PROGRAM #6
For One Sprinkler System
Viking Sprinkler | Release Zone and | 1. FIRECYCLE III Single Interlocked Preaction Multicycle System |
| ||||
System Types | Manual Release |
|
|
|
|
| |
2. FIRECYCLE III Single Interlocked Preaction Multicycle System - NYC Special | |||||||
|
|
| ZONES (Initiating Circuits) |
|
| ||
OUTPUTS | SUP 1 | SUP 2 |
| #1 | #2 | #3 | #4 |
(Indicating Circuits) |
|
|
|
|
|
|
|
Low Air | Valve Tamper |
| FIRECYCLE | Low Air | Waterflow | Manual | |
|
| ||||||
| Supervisory Zone | Supervisory Zone |
| Detector Zone | Alarm Zone | Zone | Release Zone |
#1 General Alarm |
|
|
| X |
| X | X |
|
|
|
|
|
|
|
|
#2 Supervisory Bell | X | X |
|
| X |
|
|
#3 Release Solenoid |
|
|
| X |
|
| X |
#4 N/O Solenoid |
|
|
| X | X | X |
|
|
|
|
|
|
| ||
|
| OPERATION DESCRIPTION |
|
|
| ||
Inputs: | FIRECYCLE Detector zone, Low Air Alarm zone, 1 Waterflow zone, Manual Release zone, 2 | ||||||
| Supervisory zones |
|
|
|
|
|
|
Outputs: | 1 General Alarm, 1 Supervisory Alarm, 1 Release Solenoid, and 1 N/O Solenoid |
| |||||
Operation: | Activation of FIRECYCLE Detector zone #1 will activate output #1 (General Alarm), output #3 (Release | ||||||
| Solenoid), and output #4 (N/O Solenoid) |
|
|
| |||
| Activation of Low Air Alarm zone #2 will activate output #2 (Supervisory Bell) and output #4 (N/O | ||||||
| Solenoid) |
|
|
|
|
|
|
| Activation of Waterflow zone #3 will activate output #1 (General Alarm) and output #4 (N/O Solenoid) | ||||||
| Activation of Manual Release zone #4 will activate output #1 (General Alarm) and output #3 (Release | ||||||
| Solenoid) |
|
|
|
|
|
|
| Deactivation of FIRECYCLE Detector zone #1 will start soak timer, when timer cycle is complete | ||||||
| output #3 (Release Solenoid) is deactivated |
|
|
| |||
| Activation of Low Air Supervisory Zone #1 or Valve Tamper Supervisory zone #2 will activate output #2 | ||||||
| (Supervisory Bell) |
|
|
|
|
|
|
NOTES:
1.Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
2.Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.
3.Leave EOLR (provided) on all unnused circuits.
4.See the instruction manual for circuit information, panel limits, and battery sizing.
5.For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.
6.See instruction manual for proper programming.
7.See specific system type data page for proper pressure switch settings.
8.Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.
9.Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.
10.Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.
11.Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.
30