Viking VFR-400 instruction manual PROGRAM #6

Models: VFR-400

1 58
Download 58 pages 63.79 Kb
Page 30
Image 30
PROGRAM #6

VFR-400 • 5403548 • REV D • 10/07

PROGRAM #6

For One Sprinkler System

Viking Sprinkler

Release Zone and

1. FIRECYCLE III Single Interlocked Preaction Multicycle System

 

System Types

Manual Release

 

 

 

 

 

2. FIRECYCLE III Single Interlocked Preaction Multicycle System - NYC Special

 

 

 

ZONES (Initiating Circuits)

 

 

OUTPUTS

SUP 1

SUP 2

 

#1

#2

#3

#4

(Indicating Circuits)

 

 

 

 

 

 

 

Low Air

Valve Tamper

 

FIRECYCLE

Low Air

Waterflow

Manual

 

 

 

Supervisory Zone

Supervisory Zone

 

Detector Zone

Alarm Zone

Zone

Release Zone

#1 General Alarm

 

 

 

X

 

X

X

 

 

 

 

 

 

 

 

#2 Supervisory Bell

X

X

 

 

X

 

 

#3 Release Solenoid

 

 

 

X

 

 

X

#4 N/O Solenoid

 

 

 

X

X

X

 

 

 

 

 

 

 

 

 

OPERATION DESCRIPTION

 

 

 

Inputs:

FIRECYCLE Detector zone, Low Air Alarm zone, 1 Waterflow zone, Manual Release zone, 2

 

Supervisory zones

 

 

 

 

 

 

Outputs:

1 General Alarm, 1 Supervisory Alarm, 1 Release Solenoid, and 1 N/O Solenoid

 

Operation:

Activation of FIRECYCLE Detector zone #1 will activate output #1 (General Alarm), output #3 (Release

 

Solenoid), and output #4 (N/O Solenoid)

 

 

 

 

Activation of Low Air Alarm zone #2 will activate output #2 (Supervisory Bell) and output #4 (N/O

 

Solenoid)

 

 

 

 

 

 

 

Activation of Waterflow zone #3 will activate output #1 (General Alarm) and output #4 (N/O Solenoid)

 

Activation of Manual Release zone #4 will activate output #1 (General Alarm) and output #3 (Release

 

Solenoid)

 

 

 

 

 

 

 

Deactivation of FIRECYCLE Detector zone #1 will start soak timer, when timer cycle is complete

 

output #3 (Release Solenoid) is deactivated

 

 

 

 

Activation of Low Air Supervisory Zone #1 or Valve Tamper Supervisory zone #2 will activate output #2

 

(Supervisory Bell)

 

 

 

 

 

 

NOTES:

1.Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.

2.Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.

3.Leave EOLR (provided) on all unnused circuits.

4.See the instruction manual for circuit information, panel limits, and battery sizing.

5.For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.

6.See instruction manual for proper programming.

7.See specific system type data page for proper pressure switch settings.

8.Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.

9.Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.

10.Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.

11.Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.

30

Page 30
Image 30
Viking VFR-400 instruction manual PROGRAM #6