One Man Walktest
This display allows the user to select system mode NORMAL or ONE MAN WALKTEST by pressing the SELECT button to toggle back and forth from NORMAL to ONE MAN WALKTEST. When the desired mode is displayed, press the SET button. If ONE MAN WALKTEST is selected for test purposes, the display must be restored to the NORMAL setting after the test is completed by toggling to it using the SELECT button.
After 30 minutes of no activity the panel automatically reverts to normal.
SET
SELECT
FUNCTION
After selecting NORMAL or ONE MAN WALKTEST, press the SET button to set that mode.
Press the SELECT button to toggle between NORMAL and CROSS ZONED.
Press the bottom button to skip to the next function.
After selecting the operating mode or pressing the FUNCTION button a display similar to the following will appear in the display window:
P
R
O
G
R
A
M
#
1
VFR-400 Standard Program Information
The
Notes:
The release discharge time is continuous for all programs not employing the Firecycle feature. The default soak timer for the Firecycle feature is continuous.
The following is an explanation of how the various programs operate and information about the types of
devices that are to be connected to the input and output zones. If none of the standard programs are acceptable for the installation required, select the custom program #0 then press the SET button. This will allow the user to custom program the panel. Turn to
page 45 for custom program information. |
| |
| Type | Description |
Alarm Zones | Detection | Smoke Detectors, Spot Type Heat Detectors |
| Waterflow | PS10 Pressure Switch |
| Linear Heat | Cable Type Heat Detectors |
| Manual Release | Pull Stations |
| Firecycle | Viking normally closed heat detectors |
Supervisory Zones | Supervisory | Valve Tamper, Low Air, High Air, Room Temperature |
| Low Air supervisory | Low Air Switch |
| High Air | High Air Switch |
| Tamper | Valve Tamper Switch |
| Low Air Alarm * | PS10, PS40 |
* Not available on Supervisory Zones Sup 1 or Sup 2
17