Viking instruction manual VFR-400/PFC-7500Interconnection Drawing, Panel Panel

Models: VFR-400

1 58
Download 58 pages 63.79 Kb
Page 58
Image 58
PANEL PANEL

VFR-400 • 5403548 • REV D • 10/07

Connection Procedure for Battery Charging Current and Voltage

1) To measure the battery charging voltage:

Place a voltmeter across the battery terminals as shown in FIG. 4

2) To measure the battery charging current:

Place a current meter in series with the battery terminals as shown in FIG. 5.

PANEL PANEL

VOLT

CURRENT

METER

METER

 

DWG# 3527-9

Connection Drawing for Central Station and Remote Station Operation

VFR-400/PFC-7500 Interconnection Drawing

**Or other UL864 9th Edition listed stand alone DACT connected as shown and installed in the same room within 20 feet of the VFR-400 and with interconnecting wiring in conduit.

See PFC-7500 Manual 8910225 for programming information.

See PFC-7500 Manual 8910227 for installation instructions.

Note:PFC-7500 requires RA-7690 LCD Annunciator for programming.

The VFR-400 and PFC-7500 shall be installed in the same room within 20 feet of each other and the interconnecting wires shall be in conduit.

 

 

 

MAIN

PFC-7500

 

 

 

 

 

 

BACKUP

 

 

 

 

 

 

J4

J5

 

 

 

 

 

 

TELEPHONE CONNECTIONS

 

 

 

 

 

 

 

 

 

 

U21

 

 

 

 

 

 

 

EPROM SOCKET

 

 

 

 

 

OUTPUT 1

OUTPUT 2

 

 

 

 

 

 

 

J11

1

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

3

120 VAC

AC AC B+

BO

RED YEL

GRN BLK Z1A+ Z1A- Z1B+ Z1B- Z2+ Z2- Z3+ Z3- Z4+ Z4- Z5+ Z5-

N/C COM N/O N/C COM N/O

 

4

 

J12

WLT

 

 

 

 

 

60 HZ

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

350mA

S S

 

 

S S S S S S S S S S S S

 

 

 

 

 

 

 

 

 

AC MODE

ZONE 1

3.3K EOLR

ZONE 2

3.3K EOLR'S FROM PFC-7500

ZONE 3

ZONE 4

58

Page 58
Image 58
Viking instruction manual VFR-400/PFC-7500Interconnection Drawing, Panel Panel