Viking VFR-400 Dedicated Supervisory Zones, Notification/Release Circuits, Low/Missing Battery

Models: VFR-400

1 58
Download 58 pages 63.79 Kb
Page 8
Image 8

VFR-400 • 5403548 • REV D • 10/07

Normal standby current - approximately 4.0 mA

Standby voltage - 25VDC maximum, 13.4 minimum

Maximum short circuit current - approximately 36mA

Maximum Impedance for Alarm - 1400 ohms

Normal supervisory current - approximately 4mA

Low current trouble activation - approximately 3.3mA

Alarm activation current - approximately 10mA

Ripple voltage - .4 VDC

Maximum operating voltage range: 22.5 - 25.9V DC

Frequency - continuous

* In programs 6-9, Zone 1 is a normally closed zone for Firecycle® Detectors

Dedicated Supervisory Zones

For dry contact supervisory devices such as tamper, low air, or high air switches

2 Class B Style B circuit, latching

Power limited, current limited

End-of-Line resistance - 5.1K ohms

Ripple Voltage - .1 VDC

Frequency - continuous

Maximum voltage - 25VDC

Maximum short circuit current - approximately 36mA

Maximum line resistance - 100 ohms

Normal supervisory current - approximately 4mA

Low current trouble activation - approximately 3.3mA

Supervisory current condition - approximately 10mA

(Does not include power for any auxiliary devices)

Notification/Release Circuits

The output circuits of the VFR-400 are Non-coded. This allows the use of visual and audible appliances on the same circuit. If temporal notification appliances are required for evacuation, selectable tone appliances such as the AMSECO H24W horn or SH24W Series strobe/horns or a temporal module such as AMSECO TMP1-3A or equivalents should be used.

The notification outputs do not provide synchronization. If synchronization is required, use AMSECO SMD10-3A synchronization module or equivalent, as identified on page 55. The notification appliances shall be compatible with the sync module selected. The current requirements of the appliances, wire gauge, and length of wire run determine the maximum number of appliances that can be connected to one NAC and/or sync module. The maximum cannot exceed 1 amp or whatever the sync module selected can support, whichever is lower. The sync module shall be installed as per manufacturers instructions. Equivalent sync modules are shown on page 55.

4 Class B Style Y (Class A Style Z module available for notification)

Reverse polarity upon activation

Power limited, Current limited

24 VDC Regulated, rated 1 amp each, 2.5 amps total for all 4 circuits

End-of-Line-Resistor - 5.1k ohms

Frequency - continuous

Maximum voltage - 27 VDC

Ripple voltage - .3 VDC

Maximum resistance for outputs programmed as RELEASING:

1divided by the current draw of the solenoid when activated

Normal standy supervisory current - approximately .38mA

Low current trouble activation - .11mA

Maximum impedance - 5 Ohms

High current trouble activation - .63ma

Low/Missing Battery

Causes battery and system trouble if battery falls below 22 volts. Battery circuit is fused and reverse polarity protection is provided.

Input Power

Universal Input 120VAC, (60 Hz, 165VA) or 220VAC, (50 Hz, 185VA) 15 Amp Branch Line overcurrent protection required.

System trouble is also generated if voltage drops below 102V.

Backup Power Requirements

VFR-400 - Standby 121 mA, alarm 274 mA at 24VDC

8

Page 8
Image 8
Viking VFR-400 Dedicated Supervisory Zones, Notification/Release Circuits, Low/Missing Battery, Input Power