PROGRAM #4
For Two Sprinkler Systems - Operating Simultaneously
Viking Sprinkler | 2 Dual Release | 1. Single Interlocked Preaction System with Electric Release |
| ||||
System Types | Zones, Waterflow |
|
|
|
|
| |
2. Deluge System with Electric Release |
|
| |||||
| Zone, and Dual |
|
|
|
|
| |
| 3. |
| |||||
| Manual Release |
| |||||
| 4. Double Interlocked Preaction System with Electric/Pneumatic Release | ||||||
|
| ||||||
|
| ZONES (Initiating Circuits) |
|
| |||
OUTPUTS | SUP 1 | SUP 2 | #1 | #2 | #3 | #4 | |
|
|
|
|
|
| ||
Valve Tamper | Low Air | Conventional | Conventional | Waterflow | Manual | ||
(Indicating Circuits) | |||||||
| Supervisory Zone | Supervisory Zone | Detection Zone | Detection Zone | Zone | Release Zone | |
| for Systems 1 & 2 | for Systems 1 & 2 | for System 1 | for System 2 |
|
| |
#1 General Alarm |
|
| X | X | X | X | |
#2 Release Solenoid #1 |
|
| X | X |
| X | |
#3 Release Solenoid #2 |
|
| X | X |
| X | |
#4 Waterflow |
|
|
|
| X |
| |
|
|
|
|
|
| ||
|
| OPERATION DESCRIPTION |
|
|
| ||
Inputs: | 2 Conventional Detection zones, 1 Waterflow zone, 1 Manual Release zone, 2 Supervisory zones | ||||||
Outputs: | 1 General Alarm, 1 Waterflow, 2 Release Solenoids |
|
|
| |||
Operation: | Activation of Conventional Detection zone #1 or #2 or Manual Release zone will activate output #2 | ||||||
| (Release Solenoid #1) and output #3 (Release Solenoid #2) and output #1 (General Alarm) | ||||||
| Activation of Waterflow zone #3 will activate output #4 (Waterflow) |
|
| ||||
| Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will operate | ||||||
| supervisory trouble relay |
|
|
|
|
NOTES:
1.Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #2 (Release Solenoid) and output #3 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
2.Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.
3.Leave EOLR (provided) on all unnused circuits.
4.See the instruction manual for circuit information, panel limits, and battery sizing.
5.For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.
6.See instruction manual for proper programming.
7.See instruction manual for list of compatible smoke detectors.
8.See specific system type data page for proper pressure switch settings.
26