Service Use
NFPA 13 - Automatic Sprinkler
NFPA 15 - Water Spray Fixed System
NFPA 16 - Foam Water Sprinkler and Foam Water Spray
NFPA 72 - National Fire Alarm Code
•Local
•Remote Station (protected premise unit)
•Central Station (protected premise unit) NFPA 750 - Water Mist
Listings And Approvals
Terminals
•All terminals capable of handling #14 AWG wire
•All terminations have transient protection
•All four initiating device circuit terminals capable of handling linear heat detection.
Relay Outputs
•Common system alarm contacts SPDT rated 3 Amps, 30VDC resistive
•Common supervisory contacts SPST, N.O. rated 3 Amps, 30VDC resistive
•Common system trouble contacts SPDT rated 3 Amps, 30VDC resistive
•Common system waterflow contacts SPST, N.O. rated 3 Amps, 30VDC resistive
Auxiliary Power
•Auxiliary Power - 24VDC regulated. Rated 200 mA max. Current limited
•Resettable for
Annunciator Connection
•Auxiliary Power - 24VDC regulated. Rated 200 mA max. Current limited for
•
•Maximum 2000' with 22 AWG, 4000' with 20 AWG shielded cable
Optional Accessories
CA2Z module (Class A initiating device circuit)
Converts two Class B initiating device circuits to two Class A circuits.
CAM Module (Class A Indicating Appliance Circuit)
Converts indicating appliance circuit from Class B to Class A. One model CAM (Class A Module) is required for each circuit. (Do not use this on an output programmed as “TROUBLE BELL”.)
Activated by 24VDC Indicating and/or Releasing, polarity reversing circuits. The module provides a
Connects to
Basic Operation
In addition to the following events, the panel also provides an output via the
Initiating Device Circuits Alarm Condition
An increase of current on any alarm initiating device circuit to approximately 10 mA or greater will result in the following:
Alarm (Except zones programmed as LOW AIR ALARM):
1)Activation of the common alarm relay contacts.
2)Activation of the output circuit(s) which are mapped to the initiating device circuit(s). Providing all zone(s) necessary for the activation of those circuits is in alarm
3)“ALARM” and zone # displayed on LCD.
4)Activation of the red ALARM LED in a flashing mode as well as corresponding zone. NOTE: The ALARM LED will continue to flash until the Signal Silence button is pushed. The silence button will remove power from all outputs set up as Indicating except those activated by zones programmed as Waterflow.
5)Activation of zones programmed as waterflow will operate the common waterflow relay contacts in addition to the above. Note: If Zone 1 is programmed as Firecycle, an open circuit will result in the above.
9