Viking VFR-400 instruction manual PROGRAM #12

Models: VFR-400

1 58
Download 58 pages 63.79 Kb
Page 42
Image 42

 

 

VFR-400 • 5403548 • REV D • 10/07

 

 

 

 

 

 

 

 

 

 

 

 

PROGRAM #12

 

 

 

 

 

 

 

 

 

 

 

 

For One Sprinkler System

 

 

 

Viking Sprinkler

2 Cross Release

1. Single Interlocked Preaction System with Electric Release

 

System Types

Zones, Waterflow

 

 

 

 

 

2. Deluge System with Electric Release

 

 

 

Zone, and Manual

 

 

 

 

 

 

3. Non-Interlocked Preaction system with Electric Release

 

 

Release Zone

 

 

 

 

 

 

4. Double Interlocked Preaction System with Electric/Pneu-Lectric Release

 

 

 

 

ZONES (Initiating Circuits)

 

 

OUTPUTS

SUP 1

SUP 2

#1

#2

#3

#4

(Indicating Circuits)

 

 

 

 

 

 

Valve Tamper

Low Air

Conventional

Conventional

Waterflow

Manual

 

 

Supervisory Zone

Supervisory Zone

Detection Zone

Detection Zone

Zone

Release Zone

#1 General Alarm

 

 

X

X

 

X

 

 

 

 

 

 

 

#2 Waterflow

 

 

 

 

X

 

#3 Release Solenoid

 

 

X X

X X

 

X

#4 Supervisory Bell

X

X

 

 

 

 

 

 

 

 

 

 

 

 

OPERATION DESCRIPTION

 

 

 

Inputs:

2 Conventional Detection zones, 1 Waterflow zone, 1 Manual Release zone, 2 Supervisory zones

Outputs:

1 General Alarm, 1 Waterflow, 1 Release Solenoid, 1 Supervisory Bell

 

 

Operation:

Simultaneous activation of both the Conventional Detection zone #1 and the Conventional Detector

 

zone #2 will activate output #3 (Release Solenoid) and output #1 (General Alarm)

 

 

Activation of Conventional Detection zone #1 will activate output #1 (General Alarm)

 

 

Activation of Conventional Detection zone #2 will activate output #1 (General Alarm)

 

 

Activation of Waterflow zone #3 will activate output #2 (Waterflow)

 

 

 

Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1

 

(General Alarm)

 

 

 

 

 

 

Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will activate output

 

#4 (Supervisory Bell)

 

 

 

 

 

 

 

 

 

 

XX = Cross-Zoned

NOTES:

1.Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.

2.Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.

3.Leave EOLR (provided) on all unnused circuits.

4.See the instruction manual for circuit information, panel limits, and battery sizing.

5.For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.

6.See instruction manual for proper programming.

7.See instruction manual for list of compatible smoke detectors.

8.See specific system type data page for proper pressure switch settings.

42

Page 42
Image 42
Viking VFR-400 instruction manual PROGRAM #12