Viking VFR-400 instruction manual Test Procedure Canada

Models: VFR-400

1 58
Download 58 pages 63.79 Kb
Page 13
Image 13
Test Procedure

VFR-400 • 5403548 • REV D • 10/07

have activated. Pressing the SIGNAL SILENCE button changes the flashing Red Zone LED to steady on and the flashing Red Output LED mapped to that zone off unless the output is programmed as RELEASE. In addition, the Yellow ALARM/ SILENCE LED will light.

Any zone programmed as WATERFLOW is considered non-silenceable so the signal and buzzer silence buttons will have no effect on the flashing zone and output LED's. A buzzer on the annunciator sounds for any trouble condition. When the panel has a trouble or supervisory condition, pressing the SILENCE/LAMP TEST button silences the condition at the panel and all annunciators. When the panel is in a normal state, pressing the SILENCE/LAMP TEST button can be used to test the LED's.

The release panel supervises and communicates with the annunciator via separate connections for the RS-485 communication and 24VDC power requirements of the RA-4410-RC. Separate cables should be used for power and communication. Shielded cable shall be used for the communication line. Up to three annunciators can be connected to one panel. A rotary switch is provided on the panel to indicate how many annunciators are connected. Another rotary switch is on the annunciator to set the address. The annunciators must be addressed consecutively. See page 54 for wiring information. Refer to bulletin #8840024 for installation instructions and maximum wire run.

Test Procedure

The system should be inspected, tested, and maintained in accordance with NFPA-72 National Fire Alarm Code, Chapter 10 and any other requirements of the local authority having jurisdiction.

Test Procedure (Canada)

The system should be inspected, tested, and maintained in accordance with ULC Standard CAN/ULC-S536 and any other requirements of the local authority having jurisdiction.

Testing should be done as a minimum as described below:

1)Notify the fire department or other receiving station if alarm, supervisory and/or trouble signals are transmitted.

2)Notify the proper building personnel so that audible and/or visual signals can be ignored.

3)If the release panel is monitored by a building fire alarm panel, take appropriate action to eliminate any unwanted events.

4)Momentarily open each of the following circuits.

a)Each initiating device zone

b)Supervisory circuit

c)Indicating Appliance/Releasing circuit - observe that this results in a trouble condition and all indicators operate as described in the appropriate preceding section for the particular circuit that is faulted.

5)Move the PROGRAM switch down. The LCD should respond: “LOOK AT HISTORY?”. Press the FUNCTION button until the display reads PASSWORD=000. Enter password if changed from factoy or press the SET button three times. Press the FUNCTION (bottom) button until the LCD reads “SYSTEM MODE: NORMAL”. Press the SELECT button. The LCD will read “SYSTEM MODE:

ONE MAN WALKTEST”. Press the SET button then move the PROGRAM switch up. The panel will respond with “ONE MAN WALKTEST” and the time. The trouble LED will light. Any output described as “RELEASING” will automatically be disabled.

Failure to enter the walktest mode and subsequent operation of initiating zones may result in a release.

After 30 minutes of no activity in the walk test mode the panel automatically reverts to normal operation.

6)Operate each initiating device on all zones. All audible and visual alarm devices should operate for about 3 seconds. Then the system will automatically reset allowing the user to go to the next initiating device.

7)Operate each initiating device on the supervisory circuit. Observe that all the indications described in the section on supervisory conditions occur.

8)Move the PROGRAM switch down again. The LCD should respond: “LOOK AT HISTORY?”

Press the FUNCTION button until the display reads PASSWORD=000. Enter password if changed from factory or press the SET button three times.

Press the FUNCTION (bottom) button until the LCD reads: “SYSTEM MODE: ONE MAN WALKTEST”

Press the SELECT (middle) button. The LCD will read: “SYSTEM MODE: NORMAL”

Press the SET (top) button then restore the PROGRAM switch to the up position. The LCD will show the normal banner message.

9)All audible and visual indicators should be off.

10)Notify all building, fire department, and/or other receiving station personnel that the test has concluded.

Maintenance: Test batteries per local and national standards. At a minimum replace batteries every four (4) years or sooner depending on test results. The date of purchase shall be marked on all batteries.

13

Page 13
Image 13
Viking VFR-400 instruction manual Test Procedure Canada