| LOW AIR |
|
|
|
|
VALVE | PRESSURE | CONVENTIONAL WATER | WATER | ||
SUPERVISORY | |||||
TAMPER | SWITCH |
| DETECTION | FLOW | FLOW |
SUPERVISORY SYSTEMS CONVENTIONAL SYSTEM 2 | SWITCH | SWITCH | |||
SYSTEMS | 1&2 | DETECTION |
| SYSTEM 1 | SYSTEM 2 |
1&2 | 09472 | SYSTEM 1 |
| 09470 | 09470 |
EOLR | EOLR | EOLR | EOLR | EOLR | EOLR |
5.1K 5.1K 5.1K
HOT - BLACK
NEUTRAL - WHITE
120 OHM
EARTH GROUND - GREEN
N L
5.1K
5.1K 5.1K
ZONE 1 | ZONE 2 |
24 VNR DC | AUX. POWER SUP 1 | SUP 2 | ZONE 1 | ZONE 2 | ZONE 3 | ZONE 4 | |
|
| 24VR DC |
|
|
|
|
|
| ZONE 1 | OUTPUT 1 |
| V FR |
|
|
| ||
| ZONE 2 | OUTPUT 2 |
|
|
| ZONE 3 | OUTPUT 3 |
|
|
|
|
| PROGRAM | RUN |
| ZONE 4 | OUTPUT 4 | MODE | MODE |
| AC POWER | SUPERVISORY 1 |
| |
| POWER TBL | SUPERVISORY 2 |
| BUZZER SILENCE |
|
|
| ||
RUN | SYSTEM TBL | COMMON ALARM |
|
|
SUP TBL | ALARM SILENCE |
| LAMP TEST | |
|
| |||
|
|
| ||
PROGRAM | GROUND | STEADY: DISCHARGED | SET | |
| FLASHING: PRE- | |||
| FAULT | DISCHARGE |
| }BUZZER SILENCE |
|
|
| SELECT | SIGNAL SILENCE |
|
|
| FUNCTION | SYSTEM RESET |
| VIEWING ANGLE |
|
|
|
TROUBLE | ALARM | SUPV | WTRFLW |
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4
COM NO NC COM NO NC COM NO COM NO
BAT+ BAT-
RED | BLACK |
BLACK | RED | BLACK | RED | BLACK | RED | BLACK | RED |
|
|
|
|
|
|
| RELAY CONTACTS |
| 5.1K |
|
| EOL | EOL | DRY CONTACTS RATED AT 3A, 30VDC | |
| EOLR |
|
| DIODE | DIODE |
| |
|
|
|
| ASSY | ASSY |
| |
GENERAL | RELEASE | RELEASE | WATERFLOW | ||||
ALARM | SOLENOID | SOLENOID |
|
| |||
|
| SYSTEM 1 | SYSTEM 2 |
|
|
DWG#14165VKG PRGM2
1.Run field wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with
2.Connect one circuit at a time and apply AC power.
3.Connect batteries to the panel.
4.Once last connection is made, move Program switch down.
5.Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.
6.To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)
7.Press the FUNCTION (bottom) button until the display reads “PROGRAM #2”.
8.Press the SELECT button until the display reads “PROGRAM #2”.
9.Press the SET button.
10.The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.
23