Viking VFR-400 instruction manual Connect one circuit at a time and apply AC power

Models: VFR-400

1 58
Download 58 pages 63.79 Kb
Page 23
Image 23
Manual background

VFR-400 • 5403548 • REV D • 10/07

 

LOW AIR

 

 

 

 

VALVE

PRESSURE

CONVENTIONAL WATER

WATER

SUPERVISORY

TAMPER

SWITCH

 

DETECTION

FLOW

FLOW

SUPERVISORY SYSTEMS CONVENTIONAL SYSTEM 2

SWITCH

SWITCH

SYSTEMS

1&2

DETECTION

 

SYSTEM 1

SYSTEM 2

1&2

09472

SYSTEM 1

 

09470

09470

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

5.1K 5.1K 5.1K

HOT - BLACK

NEUTRAL - WHITE

120 OHM

EARTH GROUND - GREEN

N L

5.1K

5.1K 5.1K

ZONE 1

ZONE 2

24 VNR DC

RS-485

AUX. POWER SUP 1

SUP 2

ZONE 1

ZONE 2

ZONE 3

ZONE 4

 

 

24VR DC

 

 

 

 

 

 

ZONE 1

OUTPUT 1

 

V FR -400

 

 

 

 

ZONE 2

OUTPUT 2

 

 

 

ZONE 3

OUTPUT 3

 

 

 

 

 

PROGRAM

RUN

 

ZONE 4

OUTPUT 4

MODE

MODE

 

AC POWER

SUPERVISORY 1

 

SCROLL-UP

 

POWER TBL

SUPERVISORY 2

 

BUZZER SILENCE

 

 

 

RUN

SYSTEM TBL

COMMON ALARM

 

 

SUP TBL

ALARM SILENCE

 

LAMP TEST

 

 

 

 

 

PROGRAM

GROUND

STEADY: DISCHARGED

SET

SCROLL-DOWN

 

FLASHING: PRE-

 

FAULT

DISCHARGE

 

}BUZZER SILENCE

 

 

 

SELECT

SIGNAL SILENCE

 

 

 

FUNCTION

SYSTEM RESET

 

VIEWING ANGLE

 

 

 

TROUBLE

ALARM

SUPV

WTRFLW

OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4

COM NO NC COM NO NC COM NO COM NO

BAT+ BAT-

RED

BLACK

BLACK

RED

BLACK

RED

BLACK

RED

BLACK

RED

 

 

 

 

 

 

 

RELAY CONTACTS

 

5.1K

 

 

EOL

EOL

DRY CONTACTS RATED AT 3A, 30VDC

 

EOLR

 

 

DIODE

DIODE

 

 

 

 

 

ASSY

ASSY

 

GENERAL

RELEASE

RELEASE

WATERFLOW

ALARM

SOLENOID

SOLENOID

 

 

 

 

SYSTEM 1

SYSTEM 2

 

 

DWG#14165VKG PRGM2

1.Run field wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of- line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory installed EOLR on all unused circuits.

2.Connect one circuit at a time and apply AC power.

3.Connect batteries to the panel.

4.Once last connection is made, move Program switch down.

5.Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.

6.To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)

7.Press the FUNCTION (bottom) button until the display reads “PROGRAM #2”.

8.Press the SELECT button until the display reads “PROGRAM #2”.

9.Press the SET button.

10.The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.

23

Page 23
Image 23
Viking VFR-400 instruction manual Connect one circuit at a time and apply AC power