| PROGRAM #3 |
|
|
|
| |
|
|
|
|
|
|
|
|
|
| For One Sprinkler System |
|
|
|
| |
Viking Sprinkler | 2 Cross Release | 1. Double Interlocked Preaction System with |
| ||||
System Types | zones, Waterflow |
|
|
|
|
|
|
| zone, and Manual |
|
|
|
|
|
|
| Release zone |
|
|
|
|
|
|
|
| ZONES (Initiating Circuits) |
|
|
| ||
OUTPUTS | SUP 1 | SUP 2 | #1 | #2 | #3 | #4 |
|
(Indicating Circuits) |
|
|
|
|
|
|
|
Low Air | Valve Tamper | Conventional | Low Air | Waterflow | Manual |
| |
|
| ||||||
| Supervisory Zone | Supervisory Zone | Detection Zone | Alarm Zone | Zone | Release Zone |
|
#1 General Alarm |
|
| X |
|
| X |
|
#2 Waterflow |
|
|
|
| X |
|
|
#3 Release Solenoid |
|
| X X | X X |
| X |
|
#4 Supervisory Bell | X | X |
| X |
|
|
|
|
|
|
|
|
|
| |
|
| OPERATION DESCRIPTION |
|
|
|
| |
Inputs: | 1 Conventional Detection zone cross zoned with 1 Low Air Alarm zone, 1 Waterflow zone, 1 Manual |
| |||||
| Release zone, 2 Supervisory zones |
|
|
|
|
| |
Outputs: | 1 General Alarm, 1 Waterflow, 1 Release Solenoid, 1 Supervisory Bell |
|
|
| |||
Operation: | Simultaneous activation of both the Conventional Detection zone #1 and the Low Air Alarm zone #2 |
| |||||
| will activate output #3 (Release solenoid) and output #1 (General alarm) |
|
|
| |||
| Activation of Conventional Detection zone #1 will activate output #1 (General Alarm) |
|
| ||||
| Activation of Low Air Alarm zone #2 will activate output #4 (Supervisory Bell) |
|
| ||||
| Activation of Waterflow zone #3 will activate output #2 (Waterflow) |
|
|
| |||
| Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1 |
| |||||
| (General Alarm) |
|
|
|
|
|
|
| Activation of Low Air Supervisory zone #1 or Valve Tamper Supervisory zone #2 will operate output |
| |||||
| #4 (Supervisory Bell) |
|
|
|
|
| |
|
|
|
|
| XX = Cross zoned |
|
NOTES:
1.Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
2.Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.
3.Leave EOLR (provided) on all unnused circuits.
4.See the instruction manual for circuit information, panel limits, and battery sizing.
5.For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.
6.See instruction manual for proper programming.
7.See instruction manual for list of compatible smoke detectors.
8.See specific system type data page for proper pressure switch settings.
24