Viking VFR-400 instruction manual PROGRAM #10

Models: VFR-400

1 58
Download 58 pages 63.79 Kb
Page 38
Image 38

 

 

 

VFR-400 • 5403548 • REV D • 10/07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROGRAM #10

 

 

 

 

 

 

 

 

 

 

 

For One Sprinkler System- NYC Special

 

 

Viking Sprinkler

Release Zone and

 

1. SUREFIRE Single Interlocked Preaction System

 

 

System Types

Manual Release

 

 

 

 

 

 

 

2. SUREFIRE Single Interlocked Preaction System - NYC Special

 

 

Zone

 

 

 

 

 

 

 

 

3. SUREFIRE Single Interlocked Preprimed Preaction System

 

 

 

 

 

 

 

 

4. SUREFIRE Single Interlocked Preprimed Preaction System - NYC Special

 

 

 

ZONES (Initiating Circuits)

 

 

OUTPUTS

SUP 1

 

SUP 2

#1

#2

#3

#4

(Indicating Circuits)

 

 

 

 

 

 

 

Valve Tamper

 

Low Air

Conventional

Low Air Alarm

Waterflow

Manual

 

 

 

Supervisory Zone

 

Supervisory Zone

Detection Zone

Zone

Zone

Release Zone

#1 General Alarm

 

 

 

X

 

X

X

 

 

 

 

 

 

 

 

#2 Supervisory Bell

X

 

X

 

X

 

 

#3 Release Solenoid

 

 

 

X

 

 

X

#4 Trouble Bell

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERATION DESCRIPTION

 

 

 

Inputs:

1 Conventional Detection zone, 1 Waterflow zone, 1 Low Air Alarm zone, 1 Manual Release zone, 2

 

Superviosry zones

 

 

 

 

 

Outputs:

1 General Alarm, 1 Trouble Bell, 1 Release Solenoid, 1 Supervisory Bell

 

 

Operation:

Activation of Conventional Detection zone #1 will activate output #3 (Release Solenoid) and output

 

#1 (General Alarm)

 

 

 

 

 

 

Activation of Low Air Alarm zone #2 will activate output #2 (Supervisory Bell) and output #4 (N/O Solenoid)

 

Activation of Waterflow zone #3 will activate output #1 (General Alarm)

 

 

 

Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1

 

(General Alarm)

 

 

 

 

 

 

Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will activate

 

output#2 (Supervisory Bell)

 

 

 

 

 

A trouble condition will prevent output #4 (N/O Solenoid) from activating

 

 

NOTES:

1.Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.

2.Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.

3.Leave EOLR (provided) on all unnused circuits.

4.See the instruction manual for circuit information, panel limits, and battery sizing.

5.For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.

6.See instruction manual for proper programming.

7.See instruction manual for list of compatible smoke detectors.

8.See specific system type data page for proper pressure switch settings.

9.Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.

38

Page 38
Image 38
Viking VFR-400 instruction manual PROGRAM #10