D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear- ances to combustibles as specified. Framing or finishing material closer than the minimums listed must be construct- ed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).
Combustible Mantels
1/2 in. Thick Wall
Sheathing 12 in. MAX.
14 in. MEASUREMENT FROM TOP OF MIN. FIREPLACE OPENING
Figure 5.3 Clearances To Combustible Mantels Or Other Combustibles Above Appliance
Non-combustible Mantels
| 1/2 IN. |
|
| Thick Wall | 12 IN. |
| Sheathing | |
| MAX. | |
|
| |
|
| 14 IN. |
|
| MIN. |
| MEASUREMENT |
|
| FROM TOP OF |
|
| FIREPLACE |
|
| OPENING | 1 IN.MIN. |
|
| |
|
| 4 IN. |
|
| MAX. |
Figure 5.4 | Clearances To | |
|
|
Note: For
Combustible Mantel Legs Or Wall Projections Extending Past The Face Of The Fireplace
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2 IN. |
| ||||
FIREPLACE | MINIMUM 3 | FT. MAXIMUM | |||||
OPENING |
|
|
|
|
|
|
|
6 IN.
MINIMUM
Figure 5.5 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FIREPLACE |
|
| 3 IN. |
|
|
|
|
|
|
| ||||
|
| UNLIMITED | ||||||||||||
MINIMUM |
|
| ||||||||||||
OPENING |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| 7 IN. |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 5.6
Front Side Finishing Detail
1/2 IN. |
FRAMING |
NAILING TAB |
1/2 IN. |
|
Figure 5.7 Front Side Finishing Detail
20 | Heat & Glo • SLR32 • |