Top Vent - Horizontal Termination

Venting with 1 elbow WARNING

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling firestops.

ALWAYS maintain specified clearances around venting and firestop systems.

Install wall shield and ceiling firestops as specified.

Failure to keep insulation or other material away from vent pipe may cause fire.

Top Vent - Horizontal Termination

Venting with 1 elbow

V Minimum

H1 Maximum

SLR32

 

 

 

 

 

 

90 Elbow

1-1/2 ft.

457 mm

 

 

 

 

1 ft.

305 mm

3 ft.

914 mm

 

 

 

 

2 ft.

610 mm

5 ft.

1.5 m

 

 

 

 

3 ft.

914 mm

7 ft.

2.1 m

 

 

 

 

4 ft.

1.2 m

14 ft.

4.3 m

 

 

 

 

H MAX. =14 ft. (4.3 m)

V + H MAX. = 40 ft. (12.2 m)

Note: Use SLP Series components only.

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

H1

V1

Figure 7.4

Heat & Glo • SLR32 • 2269-900 Rev. E • 4/12

25

Page 25
Image 25