Quick Reference Guide - Page 24
Main setting item (cont.)
(11)Setting
•When using both cooling and heating operations and there is an indoor unit only for heating (such as floor heating), install the
(12)Setting
•This setting is not necessary for normal installation. Make this setting to invert the logic circuit in case ports A and B of the
(13)Mixing valve types and setting
•Set the time period from full close to full open of the
(14)Setting Heating/Hot Water Switching when Boiler Is Used (function code 3E)
• When boiler is used, make this setting to operate the Hydro Unit by the instruction from the boiler.
(15)Setting Heat Pump Operating Time for Hot Water Supply Operation
•Set the time period from the start of heat pump run to the start of heater energization at the beginning of hot water supply operation. If a long period is set, it takes long time for heating water.
(16)Setting Cooling ON/OFF
• Set this function when performing cooling operation.
(17)Remote controller time indication
•
(18)Setting Nighttimes Quiet Operation
•Issue an instruction for
(19)Setting Alarm Tone
• The remote controller alarm tone can be set.
Function Code List | Function Code |
|
| |||
|
| Number |
|
| ||
| Function | Hydro | Remote | Range | Default | |
| Unit | Controller | ||||
|
|
|
| |||
| Zone 1 - heating upper temperature limit °C | 1A | - | 37 ~55 | 55 | |
| Zone 1 - heating lower temperature limit °C | 1B | - | 20 ~ 37 | 20 | |
Setting | Zone 2 - heating upper limit temperature °C | 1C | - | 37 ~55 | 55 | |
Zone 2 - heating lower limit temperature °C | 1D | - | 20 ~ 37 | 20 | ||
Temperature | ||||||
Cooling mode - upper temperature limit °C | 18 | - | 18 ~ 30 | 25 | ||
Range | ||||||
Cooling mode - lower temperature limit °C | 19 | - | 10 ~ 18 | 10 | ||
| ||||||
| Hot water - upper temperature limit °C | 1E | - | 50 ~ 75 | 75 | |
| Hot water - lower temperature limit °C | 1F | - | 40 ~ 60 | 40 | |
Hot Water | Heat pump start temperature °C | 20 | - | 20 ~ 45 | 38 | |
Operation | Heat pump stop temperature °C | 21 | - | 40 ~ 50 | 45 | |
Hot Water | Temperature compensation - start outside air | 24 | - | 0 | ||
Temperature | temperature °C | |||||
|
|
|
| |||
Compensation |
|
|
|
|
| |
Compensation temperature °C | 25 | - | 0 ~ 15 | 3 | ||
Hot Water Boost | Operation time x 10 min | 08 | - | 3 ~ 18 | 6 | |
Setting temperature °C | 09 | - | 40 ~ 75 | 75 | ||
| ||||||
| Setting temperature °C | 0A | - | 70 ~ 75 | 75 | |
Anti - Bacteria | Start cycle (day) | - | 0D | 0 ~ 10 | 7 | |
Start time (hour) | - | 0C | 0 ~ 23 | 22 | ||
| ||||||
| Operation time (min) | 0B | - | 0 ~ 60 | 30 | |
| Hot water and heating switching | 22 | - | 0 | ||
Priority Mode | temperature °C | |||||
|
|
|
| |||
Boiler and heat pump switching | 23 | - | ||||
| ||||||
| temperature °C | |||||
|
|
|
|
|