Notes on System Design

Quick Reference Guide - Page 3

Notes on System Design

The input water temperature to the Hydro Unit must be 55°C or less. Especially, be careful when there is an external heating source such as a boiler.

When hot water over 55°C returns, it may result in a failure of the unit or water leakage.

The flow rate of the circulating water must meet the following range:-

11 and 14 kW

17.5 L/minute or more

8 kW

13 L/minute or more

If the flow rate becomes less than the minimum, the protective device is activated to stop operation. Ensure the flow rate with a bypass valve, etc. when you use a flow rate valve for the Hydro Unit.

Do not drive water by power other than the pump built in the Hydro Unit.

The backup heater operates supplementary to exert a prescribed capacity when the heat pump cannot exert its capacity at a low outside temperature.

Install the Hydro Unit and water pipes in a place in which they do not freeze.

Make the water circuit closed. Never use it as an open circuit.

To prevent damage to the system during outdoor defrost the circulating water must be 20 litres or more. If total water amount is not enough, the unit may not function fully due to protective operation.

Options required for each function

Purpose

Toshiba Supply

Part name

Model code

 

Space Heating

-

-

 

 

 

Space Heating &

 

 

Space Cooling

-

-

(All Rooms)

 

 

Space Heating &

 

 

Space Cooling

-

-

(partly heating only)

 

 

 

 

 

 

150L Hot water cylinder

HWS-1501CSHM3-E

 

150L Hot water cylinder

HWS-1501CSHM3-UK

Domestic Hot Water

210L Hot water cylinder

HWS-2101CSHM3-E

210L Hot water cylinder

HWS-2101CSHM3-UK

 

 

300L Hot water cylinder

HWS-3001CSHM3-E

 

300L Hot water cylinder

HWS-3001CSHM3-UK

2-zone control

-

-

 

 

 

Interlocking with

Output control board kit

TBC-PCIN3E

boiler

(1)

 

Interlocking with

-

-

booster heater

 

 

Procure locally

Part name Radiator(s), Fan coil(s), Under floor heating

Fan coil(s) only

Fan coil(s) plus

Radiator(s)

or Under floor heating

Motorized 2-way

valve

Motorized 3-way

valve

Earth leakage breaker

Motorized mixing

valve

Circulator pump

Buffer tank

Boiler

Electric heater

Page 3
Image 3
Toshiba A09-01P manual Notes on System Design, Options required for each function, and 14 kW, 8 kW, Purpose, Toshiba Supply