Electrical supply / cable specifications

Quick Reference Guide - Page 14

Electrical supply / cable specifications

Wiring specifications (power line)

Description

 

POWER

Maximum

Installation

 

SUPPLY

current

fuse rating

 

 

 

 

 

 

 

 

14 kW

230 V ~ 50 Hz

22.8 A

25 A

Outdoor unit power

11 kW

230 V ~ 50 Hz

22.8 A

25 A

 

8 kW

230 V ~ 50 Hz

20.8 A

25 A

Outdoor-Hydro

 

 

Hydro inlet heater

3 kW

230 V ~ 50 Hz

13 A

16 A

6 kW

400 V 3N ~ 50 Hz

15 A (13 A x 2P)

25 A

power

9 kW

400 V 3N ~ 50 Hz

23 A (13 A x 3P)

25 A

 

Hydro cylinder heater power

230 V ~ 50 Hz

12 A

16 A

Hydro - cylinder

 

12 A

Cable size

Connection

destination

 

 

 

 

 

 

 

2.5 mm² or more

 

 

 

 

 

2.5 mm² or more

L

,

N

 

 

2.5 mm² or more

 

 

 

 

 

1.5 mm² or more

1

,

2

,

3

1.5 mm² or more

L

,

N

 

(TB02)

2.5 mm² or more

L1

,

L2

,

L3

2.5 mm² or more

N

(TB02)

1.5 mm² or more

L

,

N

(TB03)

1.5 mm² or more

1

,

2

(TB03)

Wiring specification (control line)

Description

Line spec

Maximum

current

 

 

3-way valve control

2 line or 3 line

100 mA

 

 

 

Mixing valve control

3 line

100 mA

 

 

 

2-zone thermo sensor

2 line

100 mA

Cylinder thermo sensor

2+GND (shield

100 mA

wire)

 

 

Second remote controller

2 line

50 mA

Maximum length

12 m

12 m

5m

5m

50m

Cable Size

0.75mm² or more

0.75mm² or more

0.75mm² or more

0.75mm² or more

0.75mm² or more

Connection destination

7

,

8

,

9

(TB05)

 

1

,

2

,

3

or

,

 

,

 

2

3

4

(TB04)

C , D (TB06)

A , B (TB06)

1 , 2 (TB07)

Control parts specifications

Description

Power

Maximum

Type

 

 

current

 

Motorized 3-way valve (for

AC 230 V

100 mA

Spring return type Note: 3-wire SPST and SPDT type can be

hot water)

used by changing the function code.

 

 

 

 

 

 

Motorized 2-way valve (for

AC 230 V

100 mA

spring return type (normally open )

cooling)

 

 

 

Motorized mixing valve type

AC 230 V

100 mA

60 sec 90º. SPDT type Note: SPST and 20 to 240 sec type

1 (for 2-zone)

 

 

can be used by changing the function code.

Output line specifications

Description

Output

Maximum

Max

Maximum

current

voltage

length

 

 

External pump No. 1

AC230V

1 A

12 m

 

 

 

 

 

External booster heater

AC230V

1 A

12 m

 

 

 

 

 

Boiler control

Non-

0.5 A

AC230 V

12 m

voltage

 

 

 

1 A

DC24 V

12 m

 

contacts

ALARM Output

Non-

0.5 A

AC230 V

12 m

voltage

 

 

 

1 A

DC24 V

12 m

 

contacts

Operation Output

Non-

0.5 A

AC230 V

12 m

voltage

 

 

 

1 A

DC24 V

12 m

 

contacts

Defrost Output

Non-

0.5 A

AC230 V

12 m

voltage

 

 

 

1 A

DC24 V

12 m

 

contacts

 

 

 

 

Interlocked with the Hydro Unit pump

Output as required when outdoor air temperature is -20°C or less

Output as required when outdoor air temperature is -10°C or less