Toshiba A09-01P manual Settings by Purpose cont, Test Run, Settings for 2-zonetemperature control

Models: A09-01P

1 31
Download 31 pages 32.73 Kb
Page 27
Image 27
Settings by Purpose (cont)

Quick Reference Guide - Page 27

Settings by Purpose (cont)

Settings for 2-zone temperature control

Procure a motorized mixing valve locally and perform piping. Connect the valve cables (as described in Electrical section).

Procure a buffer tank locally.

Procure a water pump locally, and connect its cables (as described in Electrical section).

To inhibit interlocking the water pump with the internal pump of the Hydro Unit, set DIP SW10-3 on the Hydro Unit board to OFF.

• Set DIP SW12-3 on the Hydro Unit board to ON.

Attach the temperature sensor (TFI) connected to terminals TB06 C and D of the Hydro Unit near the hot water inlet of the Hydro Unit.

Contact the temperature sensor closely with the pipe, fix it with aluminium tape or the like, and then perform insulation treatment for the sensor.

Fix TFI sensor on the room heating supply pipe by using the connector procured in locally.

Cover the cables with insulation tube (minimum 1 mm) or conduit so that the user cannot touch them directly.

Connect the functional earth wire of TFI sensor in the tank unit.

Cover the TFI sensor's cables and sensor with insulation tube (minimum 1 mm) shown in the diagram on the right.

Test Run

Use operation buttons usually to conduct a test run.

If the outside air temperature or water temperature is outside the setting value range, press the TEST Settings for 2-zone temperature control button on the remote controller and then start a test run. Since the protection setting is disabled in the TEST mode, do not continue a test run longer than 10 minutes.

Press the TEST Test Run button on the remote controller. An indication “TEST” appears on the remote controller.

Press the ZONE1, 2 Manual background button and select “heating” with the OPERATE MODE Manual background button.

The pump is activated in 30 seconds.

If air is not released completely, the flow rate switch is activated to stop operation. Release air again according to the piping procedure. Little air bite is discharged from the purge valve.

Check that the air bite sound disappears.

Check that the hydraulic pressure has become the predetermined pressure 0.1 to 0.2 MPa (1 to 2 bar). If the hydraulic pressure is insufficient, replenish water.

Heating operation starts. Check that the hydro unit starts heating.

Press the OPERATE MODE Manual background button and select “cooling.”

Cooling operation starts. Check that the hydro unit starts cooling and that the floor heating system is not cooled.

Press the ZONE1, 2 Manual background button to stop operation.

Press the HOT WATER Manual background button to start hot water supply operation.

Check that there is no air bite.

Check that hot water is present at the connection port of the hot water cylinder.

Press the HOT WATER Manual backgroundbutton to stop the hot water supply operation.

Press the TEST Manual background button to exit the test mode.

Page 27
Image 27
Toshiba A09-01P Settings by Purpose cont, Test Run, Settings for 2-zonetemperature control, Quick Reference Guide - Page