Function Code List (cont.)

Function Code List (cont.)

 

Function

 

 

 

Outside temperature T1 °C

 

Outside temperature T2 °C

 

Outside air temperature T3 °C

Heating

Setting temperature A at -20 °C

Setting temperature B at T1°C

Auto Curve

Setting temperature C at T2°C

Settings

 

Setting temperature D at T3°C

 

Setting temperature E at +20°C

 

Ratio of Zone 2 in Zone 1 Auto mode (%)

 

Temperature shift of entire Auto curve (°C)

Frost Protection

Function 0 = Valid; 1 = Invalid

Setting temperature °C

 

 

Back up heater downtime. 0=5min; 1=10min;

Back Up Heater

2=15min; 3=20min

Control

Back up heater uptime. 0=10min; 1=20min;

 

 

2=30min; 3=40min

 

 

 

Zone Selection: 0=Zones 1 and Zone 2;

 

1=Zone 1 Only

Night Setback

Change Setback temperature °C

 

Start time (hour)

 

End time (hour)

 

 

 

Room temperature control adjustment. 0=Valid;

 

1=Invalid

Room Temperature

Compensation for temperature °C

 

Setting

Downtime Zone B (x 5min)

 

 

 

 

Uptime Zone C (x5min)

 

 

2 Way Valve

2 way valve activation for cooling.

0=activated during cooling;

Operation Control

1=not activated during cooling

 

 

3 Way valve

3 way valve activation.

0=activated during hot water operation;

Operation Control

1=not activated during hot water operation

 

 

2 Zone Mixing

Specified Drive Time for Mixing Valve to 90°

Valve Drive Time

open (x 10 sec)

Boiler & Heat

Boiler synchronisation with heat pump.

Pump

0=synchronised; 1=not synchronised

Synchronisation

 

Maximum

 

Operation Time of

Maximum heat pump operation time in hot

Hot Water Heat

water operation priority mode (minutes)

Pump

 

 

 

 

Activate cooling mode.

Cooling Operation

0=cooling & heating mode;

 

1=heating mode only

 

 

Quick Reference Guide - Page 25

Function Code Number

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro Unit

 

Remote

Range

 

Default

 

 

 

 

 

Controller

 

 

 

 

 

 

 

 

 

29

 

-

-15 ~ 0

 

-10

 

 

 

 

 

 

 

 

 

-

 

-

 

0

 

0

 

 

 

 

 

 

 

 

2B

 

-

0 ~ 15

 

10

 

2C

 

-

20

~ 55

 

40

 

2D

 

-

20

~ 55

 

35

 

 

 

 

 

 

 

 

 

2E

 

-

20

~ 55

 

30

 

 

 

 

 

 

 

 

 

2F

 

-

20

~ 55

 

25

 

 

 

 

 

 

 

 

 

30

 

-

20

~ 55

 

20

 

31

 

-

0 ~ 100

 

80

 

27

 

-

-5 ~ 5

 

0

 

 

 

 

 

 

 

 

 

3A

 

-

0

~ 1

 

1

 

 

 

 

 

 

 

 

3B

 

-

8 ~ 20

 

15

 

 

 

 

 

 

 

 

 

33

 

-

0

~ 3

 

1

 

 

 

 

 

 

 

 

 

34

 

-

0

~ 3

 

0

 

 

 

 

 

 

 

 

 

58

 

-

0

~ 1

 

0

 

 

 

 

 

 

 

 

26

 

-

3 ~ 20

 

5

 

 

 

 

 

 

 

 

-

 

0E

0 ~ 23

 

22

 

-

 

0F

0 ~ 23

 

06

 

 

 

 

 

 

 

 

 

-

 

02

0

~ 1

 

0

 

 

 

 

 

 

 

 

 

35

 

-

1

~ 5

 

1

 

 

 

 

 

 

 

 

36

 

-

1 ~ 24

 

6

 

 

(5 ~ 120mins)

 

 

 

 

 

 

 

 

37

 

-

1 ~ 24

 

6

 

 

(5 ~ 120mins)

 

 

 

 

 

 

 

 

3C

 

-

0

~ 1

 

0

 

 

 

 

 

 

 

 

 

54

 

-

0

~ 1

 

0

 

 

 

 

 

 

 

 

0C

 

-

3 ~ 24

 

6

 

 

 

 

 

 

 

 

 

3E

 

-

0

~ 1

 

0

 

 

 

 

 

 

 

 

07

 

-

1 ~ 120

 

30

 

 

 

 

 

 

 

 

 

02

 

-

0

~ 1

 

1

 

 

 

 

 

 

 

 

 