Checking water volume and initial pressure of expansion vessel

The expansion vessel of the Hydro Unit has a capacity of 12 litres. The initial pressure of the expansion vessel is 0.1 MPa (1 bar). The suggested initial water charge is 0.2MPa (2 bar).

The pressure of the safety valve is 0.3 MPa (3 bar).

Verify whether the capacity of the expansion vessel is sufficient using the following expression. If the volume is insufficient, install an appropriate external expansion vessel.

V

<12 L > 12 L

Action

Internal Expansion Vessel Size OK

Internal Expansion Vessel Size too small. Install appropriate external expansion vessel

V:Necessary total vessel capacity (L)

Ɛ:

Water expansion coefficient at average hot water temperature

Vs:

Total water volume in the closed system (Do not include Hot Water Cylinder)

P1:

System pressure at tank setting position (Mpa_abs*).

 

(Pipe inner pressure during pump operation before heating device operates = water supply

 

pressure)

P2:

Maximum pressure used during operation at tank setting position (MPa_abs*).

 

(= safety valve setting pressure)

*The absolute pressure value (abs.) is obtained by adding the atmospheric pressure (0.1 MPa (1 bar)) to the gauge pressure.

Water temperature and expansion coefficient (Ɛ)

Hot water temperature

Expansion rate

(°C)

(Ɛ)

0

0.0002

4

0.0000

5

0.0000

10

0.0003

15

0.0008

20

0.0017

25

0.0029

30

0.0043

35

0.0050

40

0.0078

45

0.0100

Water temperature and expansion coefficient (Ɛ)

Hot water temperature

Expansion rate

(°C)

(Ɛ)

50

0.0121

55

0.0145

60

0.0171

65

0.0198

70

0.0229

75

0.0258

80

0.0292

85

0.0324

90

0.0961

95

0.0967

-

-

Example

Maximum Hot Water temperature: 55°C, initial

water charge: 0.2MPa and system volume: 200 L.

The calculated Vessel capacity (V) is 11.6 L:-

11.6

=

0.0145

x

200

1

-

(0.2+0.1)

 

 

 

 

(0.3+0.1)

 

 

 

 

In this case V < 12 L therefore the internal expansion vessel is sufficient.

There is no need to install an external expansion vessel.