Quick Reference Guide - Page 18
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA
The
• Connect the
Hot water cylinder connection (optional)
•Please refer to “Electrical supply/cable specifications” for fuse/cable size and for connection details.
Electrical Connection (Hot Water Cylinder Electric Heater)
•The electric heater, incorporated in the hot water cylinder, requires a separate supply to Hydro Unit.
•Connect the hot water cylinder heater electrical supply in accordance with shown below:
Live conductor: Terminal L on Terminal Block 03
Neutral conductor: Terminal N on Terminal Block 03
Earth Conductor: Earth terminal on Terminal Block 03
•Connect the hot water cylinder heater to the Hydro Unit as shown below: Live conductor to hot water cylinder: Terminal 1 on Terminal Block 03 Neutral conductor to hot water cylinder: Terminal 2 on Terminal Block 03 Earth conductor to hot water cylinder: Earth terminal on Terminal Block 03
Electrical Connection (Hot Water Cylinder temperature Sensor)
•Connect the hot water cylinder temperature sensor as shown below to terminals A & B on Terminal Block 06 in the Hydro Unit.
•Please ensure that the interconnecting cable, between the Hydro Unit and the hot water cylinder, is connected to earth at both ends of the cable using the shield wire.