Settings by Purpose

Function Code List (cont.)

 

 

 

Function

 

 

 

 

Remote Controller

24 hour or 12 hour remote control display.

 

 

Indication

0=24hr; 1=12hr

 

 

 

 

 

Outdoor Night Time

0

= Function invalid

 

1

= Function valid

 

Low Noise

 

 

Start time (hour)

 

Operation

 

End time (hour)

 

 

 

 

 

 

Alarm Tone

Tone Switching 0: OFF, 1: ON

 

 

 

 

 

Pump P2 remote

0

= Not Shown;

 

controller Display

1

= Shown

 

 

 

 

 

Outdoor Forced

0

= Forced Defrost OFF;

 

Defrost Mode

1

= Forced Defrost ON

 

 

 

 

 

Optional ON/OFF

0

= a contact “ON” = Forced stop

 

1

= b contact “OFF” = Forced stop

 

Command

2

= ON/OFF = Start / Stop

 

 

3= HA Specification

 

Outdoor Night Time

0

= Symbol displayed when mode is valid

 

(controlled by Function Code Only);

 

Mode Button

1

= Symbol displayed when mode is activated

 

 

(controlled by Function Code and Button)

 

Control Logic for

0

= Cooling thermo on – contact open;

 

Room Thermostat

1

= Cooling thermo on – contact close

Quick Reference Guide - Page 26

Function Code Number

 

 

 

 

 

 

Hydro Unit

Remote

Range

Default

Controller

 

 

 

 

 

 

 

-

05

0 ~ 1

0

 

 

 

 

-

09

0 ~ 1

0

 

 

 

 

-

0A

0 ~ 23

22

-

0B

0 ~ 23

06

 

 

 

 

 

11

0 ~ 1

1

 

 

 

 

42

-

0 ~ 1

0

 

 

 

 

46

-

0 ~ 1

0

 

 

 

 

52

-

0 ~ 3

0

 

 

 

 

56

-

0 ~ 1

0

 

 

 

 

57

-

0 ~ 1

0

 

 

 

 

Settings by Purpose

Settings when hot water supply function is not used

• When the hot water supply function is not used, set DIP SW12-1 on the Hydro Unit board to ON.

Setting for cooling

For Space Conditioning Units that do not perform cooling (radiators and Under floor heating, etc.), procure a motorized 2-way valve (for cooling) locally and attach it to the water pipe that is not used for cooling. Connect the valve cables (as described in Electrical section).

Press long the TEST Setting for cooling + SET Settings for hot water supply + SELECT Manual background switches on the remote controller to change the Hydro Unit function code, and change address 02 to 0, and then press the SET button to enable the function.

Press the TEST Manual background button to exit the setting mode.

• Stick the optional insulator for cooling to the bottom of the Hydro Unit.

Settings for hot water supply

Prepare the optional hot water cylinder.

Procure a motorized 3-way (diverter) valve locally and perform piping. Connect the valve cables (as described in Electrical section).

Set DIP SW12-1 on the Hydro Unit board to OFF.

Connect the power supply unit for the hot water cylinder heater to terminals TB03 L and N of the Hydro Unit.

Connect cables between the Hydro Unit and the hot water cylinder as follows:

Hydro Unit terminals

TB03

(1), (2), and earth —

Hot water cylinder (1), (2), and earth

 

TB06

A, B, and earth —

Hot water cylinder A, B, and earth