Alarm Indications (cont)

A09

Overheat preventive operation malfunction Auto-reset: When operation mode is changed

 

 

A11

Release preventive operation malfunction This alarm occurs when the Hydro Unit enters the forced-

stop zone 10 times.

 

 

Self-hydro unit is stopped due to alarm of other hydro unit. When alarm occurs in an hydro unit in the

 

group, other hydro units must also be stopped with refrigerant control.

P31

When alarm E03, L03 or L07 occurs in the header unit in the group, other hydro units must also be

stopped

 

 

because they do not know which header unit (remote controller) to follow.

 

Auto-reset: When the first alarm is reset

Outdoor Alarm indication

Alarm

Main failure part

Description

indication

 

 

F04

Outdoor unit discharge

When open- or short-circuit of discharge temperature sensor TD is

temperature sensor TD

detected

 

defect

 

 

F06

Outdoor unit temperature

When open- or short-circuit of heat exchanger temperature sensor

sensor TE or TS defect

TE or TS is detected

 

F08

Outdoor unit outside air

When open- or short-circuit of outside air temperature sensor TO is

temperature sensor TO

detected

 

defect

 

 

H01

Compressor breakdown

When min-Hz is reached by current release control or when short-

circuit current (Idc) is detected after direct current excitation

 

 

H02

Compressor locked

When compressor lock is detected

H03

Current detector defect

When abnormal current is detected in AC-CT or phase loss is

detected

 

 

H06

Low-pressure system defect

Ps pressure sensor defect or low-pressure protective operation

L29

Other outdoor unit faults

Other outdoor unit faults: 1) Inter-MCU communication error between

IPDU and CDB 2) abnormal GBT heat sink temperature

 

 

L31

Phase sequence error, etc.

When phase sequence of 3-phase power supply is incorrect

(thermostat OFF operation continued), etc.

 

 

P03

Abnormal outdoor unit

When abnormal temperature is detected by discharge temperature

discharge temperature

release control

 

P04

High-pressure system

When high-pressure switch , IOL is activated or when abnormality is

defect

detected by high-pressure release control by TE

 

P22

Outdoor unit fan defect

When over current or lock in outdoor unit fan drive circuit is detected

P26

Inverter Idc operation

When short-circuit protection is activated for compressor driver

devices (G-Tr, IGBT)

 

 

P29

Position detection error

When compressor motor position detection error is detected