Toshiba A09-01P manual Quick Reference Guide - Page, Set the DIP switches on the main board

Models: A09-01P

1 31
Download 31 pages 32.73 Kb
Page 19
Image 19
•Set the DIP switches on the main board.

Quick Reference Guide - Page 19

Setting DIP Switches on the Board in the Hydro Unit

Detach the front cover and the electric parts box cover of the Hydro Unit.

Set the DIP switches on the main board.

SW10

Description

 

Switch mode

 

Default setting

 

 

Alternate

 

 

 

 

1

Internal pump P1 operating

Continuous operation

OFF

ON

HP synchronized

mode

 

 

 

 

 

 

 

 

 

 

Interlocked with the

3

External P2 pump operation

Continuous operation

OFF

ON

internal pump

 

 

 

 

 

synchronized with P1.

SW11

Description

 

 

Switch mode

 

 

Default setting

 

 

 

 

Alternate

 

 

 

 

 

 

1

Internal backup heater

Operate

 

OFF

ON

Not operate

operation

 

 

 

 

 

 

 

 

 

2

Hot water cylinder heater

Operate

 

OFF

ON

Not operate

operation

 

 

 

 

 

 

 

 

 

3

Booster heater operation

Operate

 

OFF

ON

Not operate

SW12

Description

 

 

Switch mode

 

Default setting

 

 

 

Alternate

 

 

 

 

 

1

Hot water supply operation

Valid

 

OFF

ON

Invalid

2

Zone 1 operation

Valid

 

OFF

ON

Invalid

3

Zone 2 operation

Invalid

 

OFF

ON

Valid

SW13

Description

 

Switch mode

 

Default setting

 

 

 

Alternate

 

 

 

 

 

1

Type of motorized 3-way valve

2-wire spring return type

 

OFF

ON

3-wire SPDT type

3-wire SPST type

 

 

 

 

 

 

 

2

Interlocking with boiler

Invalid

 

OFF

ON

Valid

3

Auto restart for power failure

Auto restart

 

OFF

ON

Manual restart

SW02

Description

 

Switch mode

Default setting

 

 

 

Alternate

 

 

 

 

 

4

Room thermostat

Invalid

 

OFF

ON

Valid

Page 19
Image 19
Toshiba A09-01P manual Quick Reference Guide - Page, Set the DIP switches on the main board