Quick Reference Guide - Page 29
Alarm Indications
Alarm | Alarm description and generation/reset conditions | |
indication | ||
| ||
| Regular communication error between hydro unit and remote controller (system controller) If there is no | |
E03 | regular communication from the remote controller for three minutes, the hydro unit regards it as no | |
remote controller. If there is no communication from both sides, alarm E03 occurs. | ||
| ||
| successful regular communication is made | |
| Regular communication error between hydro unit and outdoor unit When serial signal from the outdoor | |
| unit cannot be received though normal serial signal is sent to the outdoor unit 1) When serial signal | |
E04 | cannot be received continuously for 60 seconds (S code communication) 2) Communication is still not | |
successful for 80 seconds through three retries if serial signal cannot be received for 20 seconds after | ||
| new communication (f code) starts When the remote controller starts operation, serial transmission | |
| starts with the new communication format. | |
| made | |
| Condensing temperature TC sensor defect | |
F03 | If | |
| ||
| Hydraulic heat exchanger inlet temperature TWI sensor defect | |
F10 | If | |
| ||
| Hydraulic heat exchanger outlet temperature TWO sensor defect | |
F11 | If | |
| ||
| Hot water cylinder temperature TTW sensor defect | |
F14 | If | |
| ||
| Floor inlet temperature TFI sensor defect | |
F17 | If | |
| ||
| Internal heater outlet temperature TWO sensor defect | |
F18 | If | |
| ||
| ||
F23 | If | |
| ||
| Hydraulic heat exchanger EEPROM defect | |
F29 | One mismatch is detected if there is no verification ACK after data write to the EEPROM Reset | |
condition: This alarm is inhibited while the unit is not working. | ||
| ||
| (When EEPROM1K is mounted, this alarm cannot be reset.) | |
F20 | Floor inlet temperature TFI sensor disconnection or wrong installation (This alarm is reset by stopping | |
operation and is checked again.) | ||
| ||
F30 | Onboard expansion IC defect This alarm is not reset automatically. | |
|
| |
| Group line in an hydro unit | |
| This alarm is checked during initial communication immediately after | |
L07 | immediately after operation start. | |
| This alarm is not reset automatically. (This alarm is inhibited while the unit is not working, but occurs | |
| again after the unit operates.) | |
L09 | Hydro unit capacity has not been set. | |
This alarm is checked immediately after | ||
| inhibited while the unit is not working, but occurs again after the unit operates.) | |
A01 | Pump defect or abnormal flow rate This alarm is not reset automatically. | |
|
| |
A02 | Excessive water temperature increase by the heating heater | |
|
| |
A03 | Excessive water temperature increase in the hot water cylinder | |
|
| |
A04 | Freezing is detected. | |
|
| |
A07 | ||
|
| |
A08 | ||
|
|