Heat & Glo LifeStyle ST-36TRB-IPI Vent Clearances and Framing, A. Pipe Clearances to Combustibles

Models: ST-36TRB-IPI

1 82
Download 82 pages 9.56 Kb
Page 36
Image 36
8 Vent Clearances and Framing

8 Vent Clearances and Framing

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles:

Between ceiling firestops

Between wall shield firestops

Around vent system

Failure to keep insulation or other material away from vent pipe may cause over heating and fire.

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

‡DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick.

‡,f wall thickness is less than 4 in. the e[isting heat shields must be field trimmed. ,f wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.

‡SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to 194 mm thick).

‡,f wall thickness is less than 4-3/8 the e[isting heat shields must be field trimmed. ,f wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required.

B. Continue Adding Vent Components

WARNING! Risk of Fire! Installation of this appliance may require the use of heat shield 385-920 above the first 900 elbow in the venting system.

The heat shield is required above the first elbow if the clearance to combustible surface above is between three (3) and four (4) inches. A shield is not required for clearances greater than four inches. See Figure 8.2.

COMBUSTIBLE

SURFACE

HEAT

3 in. MIN.

SHIELD

(76 mm)

(Required for clearances

 

between 3 and 4 inches.)

 

3 in. (76 mm) top clearance

1 in. (25 mm) clearance around A. Pipe Clearances to Combustibles vertical sections B. Continue Adding Vent ComponentsManual backgroundManual backgroundManual backgroundManual background

(DVP-SLP Pipe Shown)

Heat

3 in. (76 mm)

Shield

top clearance *

 

Heat

 

Shield

 

1 in. (25 mm)

Wall

clearance

Shield

bottom & sides

Firestop

 

 

WALL

Figure 8.2

Heat

Shield

Wall

Shield

Firestop

WALL

3 in. (76 mm) top clearance *

Heat

Shield

Manual background1 in. (25 mm) clearance bottom & sides

Fasten the shield in place using the four pilot holes provided in the part. The shield should be oriented such that the 13-1/8 inch dimension (longest dimension) is running in the same direction the elbow is pointing. The shield should be centered directly above the elbow, and positioned so that it creates a 1/2 inch airspace between the shield and the combustible surface. See Figure 8.3.

* When using SLP pipe, minimum clearances from the vent pipe to combustible materi-

als at wall shield firestops are:Top: 2-1/2 in. (64 mm) Bottom: 1/2 in. (13 mm) Sides: 1 in. (25 mm)

Figure 8.1 Horizontal Venting Clearances To Combustible Materials

36

Heat & Glo • ST-36TRB-IPI, PIER-36TRB-IPI, LCOR-36TRB-IPI, RCOR-36TRB-IPI2128-900 Rev. H • 8/11

Page 36
Image 36
Heat & Glo LifeStyle ST-36TRB-IPI owner manual Vent Clearances and Framing, A. Pipe Clearances to Combustibles