2.Top Vent - Vertical Termination No Elbow
V1 = 60 ft. Max. (18.3 m)
V1 = 3 ft. Min. (914 mm)
NOTE: If installing a vertical vent/ termination off the top of the appli- ance, the optional vertical termina- tion baffle should be used.
V1
Figure 7.7
Exhaust restrictors are recommended for these verti- cally terminated products which have excessive draft. Exhaust restrictors will compensate for high draft, and restore visual flame height. If the vent configuration has a total vertical of
Exhaust restrictor Instructions
1.Remove refractory panel and exhaust baffle from pilot side of appliance. To remove the refractory panel use a 1/4 inch nut driver and remove the two screws that secure it in place. To remove the exhaust baffle, remove the three screws securing the refractory panel in place. See Figure 7.8.
Refractory Panel
To access the exhaust opening, remove the refractory panel and exhaust baffle. To remove refractory panel, remove the two screws on top. To remove the exhaust baffle, remove the three screws securing it.
Top Vent Application
Exhaust restrictor
Note: Be sure to re- install the exhaust baffle and refractory panel after exhaust restrictor installation.
Rear Vent Application
Exhaust restrictor
Note: Be sure to re- install the exhaust baffle and refractory panel after exhaust restrictor installation.
Figure 7.8