Heatiator GC150 SERIES DIRECT VENT GAS APPLIANCE, Figure Horizontal Termination Cap Locations

Models: GC150

1 28
Download 28 pages 32.15 Kb
Page 10
Image 10
Figure 9

GC150 SERIES DIRECT VENT GAS APPLIANCE

5.Termination Cap. Vent termination must not be recessed into the wall or exterior sheeting. Figure 9 illustrates termination cap locations and

minimum dimensions for each termination applica- tion. Or, follow ANSI Z223.1, latest edition.

Figure 9

Horizontal Termination Cap Locations

Dimension Descriptions

A= Clearance above the ground, a veranda, porch, deck, or balcony - 12 inches (30 cm) minimum.

B= Clearance to window or door that may be opened - 9 inches (30 cm) minimum.

D* = Vertical clearance to ventilated soffit located above the terminal within a horizontal dis- tance of 2 feet (60 cm) from the center-line of the terminal - 18 inches (46 cm) minimum.

E* = Clearance to unventilated soffit - 12 inches

(30 cm) minimum.

F= Clearance to outside corner - 9 inches as tested.

G= Clearance to inside corner - 9 inches as test- ed.

H• = Not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally from the center-line of the regulator.

IDimension Descriptions = Clearance to service regulator vent outlet - 6 feet (1.8 m) minimum.

J= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance - 12 inches (30 cm) mini- mum.

K• = Clearance to mechanical air supply inlet - 6 feet (1.8 m) minimum.

L+ = Clearance above a paved sidewalk or paved driveway located on public property - 7 feet (2.1 m) minimum. Use of a CS will reduce this dimension to as low as 12 inches (30 cm).

M# = Clearance under veranda, porch deck, or bal- cony - 12 inches (30 cm) minimum.

+A vent must not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

#Only permitted if veranda, porch deck, or bal- cony is fully open on a minimum of 2 sides beneath the floor.

As specified in Installation Codes. Note: Local codes or regulations may require differ- ent clearances.

*30 inches/76 cm minimum distance required for vinyl soffit materials.

As specified in CGA B149 Installation Codes (1991). Note: Local Codes or Regulations may require different clearances.