B. Facing Material
•Metal front faces may be covered with
•Facing and/or finishing materials must not interfere with air flow through louvers, operation of louvers or doors, or access for service.
•Facing and/or finishing materials must never overhang into the glass opening.
•Observe all clearances when applying combustible materials.
Note: If using the optional finishing trim for the Modern Front facing, finish wall material must not be installed within 3 in. (76 mm) of the fireplace opening. See Figure 14.5.
•Seal joints between the finished wall and appliance top and sides using a 300 °F minimum sealant. Refer to Figure 14.4.
WARNING! Risk of Fire! DO NOT apply combustible ma- terials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will inter- fere with proper operation of doors and louvers.
42.25 in. (NEVO3630)
48.25 in. (NEVO4236)
1/8 in. reveal all sides
30.22 in.
6 in.
6 in.
Figure 14.3 Marble/Granite Cut Dimensions
•Figure 14.3 shows the dimensions for cutting marble/ granite if the optional Finishing Trim is not used.
•The dimensions given assume a 1/8 in. reveal around the fireplace opening.
Finish wall material may be combustible - Top and Sides
| 0 in. |
0 in. | 0 in. |
High Temperature Sealant (300° F/149° C min.)
Top and Side Seal Joint
Figure 14.4
3 in. (76 mm)
3 in.
(76 mm)
3 in.
(76 mm)
Gray shading represents clearance needed for optional Finishing Trim that may be used with the Modern Front. No facing material may be used within the shaded area.
Note: Fireplace MUST be elevated 1 1/2 in. (38 mm) off floor
Figure 14.5 Clearance for Optional FInishing Trim (Modern Front)
Heatilator • Evolution • | 55 |