Turn on Power to FIRSTVISION

Enabling FIRSTVISION to Monitor Your Building

3.3 Turn on Power to FIRSTVISION

Turn-on the power supply connected to FIRSTVISION. Refer to “FIRSTVISION Installation Instructions” on page 11 for installation information.

3.3.1What Displays After the Initial Power Up of FIRSTVISION

1.Windows® XP Embedded will start and display.

2.The software application "progress bar" will display and remain displayed until the loading of the software application and its components are complete.

NOTE: Do NOT attempt to stop this loading.

3.After the progress bar disappears; the software application will automatically start because a shortcut to the application has been placed in the product’s Startup folder.

NOTE: Do NOT remove this shortcut.

3.3.2 What You Should Know about FIRSTVISION IP Addresses

Your LAN IP address (setup with Windows Internet Protocol (TCP/IP) Properties) has a default of: 192.168.0.4.

If it is necessary to change the factory LAN IP address; refer to “Establish Communication Between Your LAN and FIRSTVISION” on page 22 for information.

The gateway that FIRSTVISION monitors (setup with Add Gateway Connection) has a factory setting of 192.168.0.3.

If it is necessary to change this factory setting; refer to “Establish Gateway Communication” on page 23 for information.

If it is necessary to change a gateway’s IP address, refer to the gateway’s respective installation manual.

3.3.3What You Should Know about FIRSTVISION Windows Settings

Windows Administrator Settings

NOTE: Do NOT change the factory boot setup for FIRSTVISION’s host computer (that is, administrator is automatically logged in at startup), or add any user accounts.

It is essential that the FIRSTVISION host computer remain configured to automatically log in the administrator account at startup, without asking for a password.

Screen Saver Settings

„Monitor Power

A Monitor Power selection should NOT be changed from the factory default settings, which all are set to Never (always on), because any setting will prevent the software application from starting automatically after a power loss.

FIRSTVISIONInstallation and Operation Manual - P/N: 53034:Rev: A2 10/29/07