Enabling FIRSTVISION to Monitor Your Building

Establish Gateway Communication

It is anticipated that the factory settings for a gateway may probably work for your application and it is recommended you use them, if possible, instead of setting up new settings. If you want to change the factory settings use the following information

NOTE: Your LAN connection must be established before you add a gateway.

How To Add a Gateway Using the Configuration Tool

The gateway can be changed here, but FIRSTVISION can monitor only one gateway.

NOTE: If you change the gateway IP address, you must re-export your building design to XML. See “How to Export Your Building Design for Copying to FIRSTVISION” in ONYX®FIRSTVISIONConfiguration Tool Manual - 53035.

NOTE: The factory default Gateway IP address setting is: 192.168.0.3. If you need to change this setting, then use the following information.

Step 1.

Start the Configuration Tool.

Step 2.

Select Tools > Gateway Configuration.

Step 3.

Enter the Gateway IP address.

Step 4.

Click OK.

Figure 3.14 Gateway Configuration

Step 5. Close the Configuration Tool.

Step 6. You should now "Copy Your Exported Building Design to FIRSTVISION".

24

FIRSTVISIONInstallation and Operation Manual - P/N: 53034:Rev: A2 10/29/07