7 Configuration continued
Example of saving a controller configuration
AirAlert96d = “Configuration”
Date =
[CONFIG] | [ADDRESS_1] | [ADDRESS_2] | [GROUP_1] |
language = 1 | txtype = 1 | txtype = 17 | tx_0 = 1 |
scrollmode = 0 | display = "ECF9 NH3 AD:01" | display = "ECF9 NH3 AD:02" | tx_1 = 2 |
relaymode = 0 | protocol = 1 | protocol = 1 | tx_2 = 0 |
password = "2967" | baudrate = 9600 | baudrate = 9600 | [EVENT_1] |
cie = 0 | databits = 8 | databits = 8 | actiontarget = 14 |
priority = 0 | stopbits = 2 | stopbits = 2 | actionrelay = 1 |
autoload = 1 | parity = 0 | parity = 0 | delaybefore = 0 |
[SLAVE] | sensortype = 65 | sensortype = 2 | delayafter = 0 |
address = 1 | fullscale = 102.000000 | fullscale = 250.000000 | cond1source = 1 |
protocol = 1 | unit = 0 | unit = 1 | cond1logic = 1 |
baudrate = 38400 | alarmAmin = 20.1000003 | alarmAmin = 20.0000000 | cond1alarm = 0 |
databits = 8 | alarmAmax = 25.0000000 | alarmAmax = 25.0000000 | [EVENT_2] |
stopbits = 2 | alarmBmin = 45.000000 | alarmBmin = 180.000000 | actiontarget = 0 |
parity = 0 | alarmBmax = 50.000000 | alarmBmax = 200.000000 | actionrelay = 1 |
| alarmCmin = 85.000000 | alarmCmin = 218.000000 | delaybefore = 255 |
| alarmCmax = 90.000000 | alarmCmax = 225.000000 | delayafter = 255 |
|
| databits = 7 | cond1source = 129 |
|
| stopbits = 2 | cond1stat = 9 |
|
| parity = 0 | cond1logic = 7 |
|
|
| cond1min = 10.0000000 |
|
|
| cond1max = 15.0000000 |
|
|
| [FIN] |
|
|
|
|
Parameters (Copying Parameters)
| 5. Copy |
| 001 |
|
| ||
|
|
| |
Tx info to Tx info |
| ||
Event to Event |
|
The copying of parameters serves to transfer one sensor’s configuration to another, or one event to a second event. This function accelerates programming on the display when two entities have identical or close properties. Tx Info to Tx Info copies a sensor’s parameters, and Event to Event copies the parameters of one event to another.
TxINFO to TxINFO
(copies the parameters of a sensor)
Tx info to Tx info source tx001 target tx002
COPY
Event to Event
Event to Event source #001 target #002
COPY
Config (Programming Display Parameters and the Access Code)
6. Config
Manual scroll mode Set Date and Time Menu francais
The CONFIG MENU is used to program the display mode, adjust the time and date, select the display language in the first window, and to edit the password in the second window.
Manning | 18 |