7 Configuration continued

Example of saving a controller configuration

AirAlert96d = “Configuration”

Date = “2006-01-09 13:51:57:”

[CONFIG]

[ADDRESS_1]

[ADDRESS_2]

[GROUP_1]

language = 1

txtype = 1

txtype = 17

tx_0 = 1

scrollmode = 0

display = "ECF9 NH3 AD:01"

display = "ECF9 NH3 AD:02"

tx_1 = 2

relaymode = 0

protocol = 1

protocol = 1

tx_2 = 0

password = "2967"

baudrate = 9600

baudrate = 9600

[EVENT_1]

cie = 0

databits = 8

databits = 8

actiontarget = 14

priority = 0

stopbits = 2

stopbits = 2

actionrelay = 1

autoload = 1

parity = 0

parity = 0

delaybefore = 0

[SLAVE]

sensortype = 65

sensortype = 2

delayafter = 0

address = 1

fullscale = 102.000000

fullscale = 250.000000

cond1source = 1

protocol = 1

unit = 0

unit = 1

cond1logic = 1

baudrate = 38400

alarmAmin = 20.1000003

alarmAmin = 20.0000000

cond1alarm = 0

databits = 8

alarmAmax = 25.0000000

alarmAmax = 25.0000000

[EVENT_2]

stopbits = 2

alarmBmin = 45.000000

alarmBmin = 180.000000

actiontarget = 0

parity = 0

alarmBmax = 50.000000

alarmBmax = 200.000000

actionrelay = 1

 

alarmCmin = 85.000000

alarmCmin = 218.000000

delaybefore = 255

 

alarmCmax = 90.000000

alarmCmax = 225.000000

delayafter = 255

 

 

databits = 7

cond1source = 129

 

 

stopbits = 2

cond1stat = 9

 

 

parity = 0

cond1logic = 7

 

 

 

cond1min = 10.0000000

 

 

 

cond1max = 15.0000000

 

 

 

[FIN]

 

 

 

 

Parameters (Copying Parameters)

 

5. Copy

 

001

 

 

 

-parameters

 

Tx info to Tx info

 

Event to Event

 

The copying of parameters serves to transfer one sensor’s configuration to another, or one event to a second event. This function accelerates programming on the display when two entities have identical or close properties. Tx Info to Tx Info copies a sensor’s parameters, and Event to Event copies the parameters of one event to another.

TxINFO to TxINFO
(copies the parameters of a sensor)

Tx info to Tx info source tx001 target tx002

COPY

Event to Event
Event to Event source #001 target #002

COPY

Config (Programming Display Parameters and the Access Code)

6. Config

Manual scroll mode Set Date and Time Menu francais

The CONFIG MENU is used to program the display mode, adjust the time and date, select the display language in the first window, and to edit the password in the second window.