7 Configuration continued

Tests (Sequential Test Mode)Test Sequence

This simple test sequence enables the user to activate each output and validate the operation of each controller key and all display pixels, as well as the different communication protocols.

Start Sim. Sequ. & Stop Sim. Sequ. (Stop Simulation)

8.Tests

Test Sequence Start Sim Sequence Maximum load

See Simulation Mode section for more details.

The simulation mode allows for the simulation of gas concentration over associated scale range on all sensors. The simulated gas concentration values are local to the controller.

Start with Tx00X (simulation starts with sensor 00X)

Confirm (simulation activation)

Maximum Load (Activation of All Controller Components)Oprt Mode (Controller Operating Mode)

8. Tests

Oprt Mode: normal

See System Operation section for more details.

1Normal (normal controller operating mode)

2Single Tx (activation of interrogation mode for a single sensor)

3Debug (activation of service mode to allow for calibration without affecting events)