8 Specifications

Power Requirements

24 Vdc, 500 mA

Operating Environment

Ordinary location

Operating Temperature Range

-4°F to 122°F (-20°C to 50°C)

Operating Humidity Range

0 to 95% RH, (non condensing)

Operating Altitude

Up to 9843 ft. (3,000 m)

Network Capacity

Up to 96 sensors, 32 per channel Channel 1, 2, and 3: MODBUS Channel 4: Modbus output to PLC

Communication (length of lines)

Up to 2,000 feet (600 m) per channel 24 AWG #9841 Belden Cable

T-tap: 65 feet (20 m) maximum per t-tap,130 feet (40 m) total

User Interface

Graphic 122x82 dot matrix backlit display

User friendly keypad

Visual Indicators

Power On

Green LED

Warn

Red LED

 

(blinking upon an event)

Alarm

Red LED

High Alarm

Red LED

Fault

Yellow LED

Tx

Amber LED

 

(blink when used)

Rx

Green LED

 

(blink when used)

Outputs

4 DPDT relays

5A, 30 Vdc or 250 Vac (resistive load)

Time Delays

0, 30, and 45 seconds, and1 to 99 minutes before and after alarm

Battery

Lithium battery, 3 volts

Enclosure

NEMA 4x, cast aluminium #A356.0T6

Overvoltage Category

II

Dimensions

9.50” (W) x 14.00” (H) x 3.50” (D)

Weight

11.4 lbs (5.2 kg)

9 Maintenance

The Manning AirAlertTM96d is a maintenance free controller. Only the sensors need periodic inspection and calibration (see sensor manual).

Periodic Inspections and Calibration

Honeywell Analytics provides its customers with specialized gas detection equipment. Beyond the warranty period, the systems must be maintained and calibrated on a regular basis (normally two times a year).

Honeywell Analytics will not assume responsibility for the interruption of service or malfunctioning of its equipment as a result of the discontinuance of maintenance and calibration services.

If unit span or zero cannot be adjusted, the sensor may be approaching its end-of-life and must be replaced. Keep an operation log of all maintenance, calibrations and alarm events.

Replacement Parts

A replacement 3V lithium battery is also available. If the memory card option is present, spare SDcards are also available.

Due to continuous evolution of our products, please contact our service department for ordering parts or for more details.

Cleaning

Clean the exterior with a soft, damp cloth. Do not use solvents, soaps or polishers.

Battery Disposal

This instrument contains a lithium battery. Do not mix with the solid waste stream. Spent batteries should be disposed of by a qualified recycler or hazardous materials handler.

Manning AirAlert-96d Gas Monitor 19073 AIRALERT96D 05/2006 Prelim REVC Copyright © 2006 Honeywell Analytics. All Rights Reserved.

21