3 Wiring

Figure 3. System Wiring

SD card datalogger

 

 

 

 

 

 

Pushbutton

 

 

EOL2

 

EOL3

 

EOL4

EOL1

RC

 

 

 

 

 

 

 

 

 

RC

 

RC

 

 

R

 

 

 

 

 

 

RC

 

 

 

 

 

 

 

 

 

R

 

R

 

 

 

In

Out

 

 

 

 

R

 

 

 

 

 

 

 

J22

V+ V-

J23

A1 B1

A2 B2 SHLD

J24

A3 B3 A4 B4

V+ V-

 

SHLD

J3

NC

 

Relay 4

 

 

NO

 

 

 

 

 

 

 

J7

NC

 

 

 

 

 

Relay 3

 

 

NO

 

 

 

 

 

Warn

 

 

 

LEDsstatusSystem

Alarm

 

 

 

High Alarm

 

 

 

 

 

 

 

End-of-line

Power

 

 

 

jumper position

Relay 1

 

Relay 2

 

 

Fault

 

 

 

 

TX

 

 

 

 

RX

J26

 

J25

 

 

 

 

 

NO

NC

NO

NC

 

Relay Outputs (J3-J7-J25-J26)

 

 

5A, 30 Vdc or 120 Vac (resistive load)

Channel 2

Channel 4

 

Normally 3+5

 

open

4+6

 

 

 

 

6

4

2

 

Previous

 

 

Normally 1+3

Channel 1

Channel 3

 

closed

2+4

 

5

3

1

 

Next

Power Requirements:

24 Vdc, 500 mA

14 AWG, 2 conductor, stranded cable (Belden 5100UE or equivalent)

Up to 10 sensors per power supply

Up to 1,000 feet max power cable length per power supply

Larger power cable and/or additional power supplies may be required for longer cable runs and/or increased number of sensors

Contact Honeywell Analytics for help with all power requirements.

Communication Requirements:

24 AWG twisted pair, shielded (Belden 9841 or equivalent)

Network can be up to 2,000 feet per channel

Avoid “T-taps” if possible

Do not exceed 65 feet per T-tap

Do not exceen 130 feet total of all T-taps

Communication wire shield must be connected to shield terminal(s) of controller (J23-J24)

Channels 1-2-3: Modbus protocol — Communicates only with Modbus devices

Channel 4: Modbus output only — No sensor can be connected to Channel 4

Manning AirAlert-96d Gas Monitor 19073 AIRALERT96D 05/2006 Prelim REVC Copyright © 2006 Honeywell Analytics. All Rights Reserved.

5