10 Relay Module (optional) continuedWiring Details
Power Supply Cable

14 AWG stranded cable or larger (see your network diagram provided by Honeywell Analytics sales department).

Communication Cable

24 AWG twisted pair (Belden # 9841 or equivalent).

Figure 11. Relay Module PCB

End of Line Resistor On the last device of the communication network, a jumper must be installed as shown.

off

1

2 DIP switches

3

4

Power

Power and TX

 

 

status LEDs

Tx Modbus

 

 

 

 

 

 

 

 

 

 

 

 

 

EOL1

RC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

Relay 8

 

Relay 7

 

Relay 6

 

Relay 5

 

Relay 4

 

Relay 3

 

Relay 2

 

Relay 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J10

J8

 

J7

 

 

 

 

 

 

 

 

 

J2

 

J1

 

 

V+ V- A

B SHLD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

NC

NO

NC

NO

NC

NO

NC

NO

NC

NO

NC

NO

NC

NO

NC

From “B” terminal of controller

to “B” terminal of next device

From “A” terminal of controller

From +24VDC terminalto “A” terminal of next device of power supply

From Ground terminal of power supply

Relay Outputs (J1-J8)

5A, 30 Vdc or 120 Vac (resistive load)

Normally 3+5

open 4+6

6 4 2

Normally 1+3 closed 2+4

5 3 1

Manning AirAlert-96d Gas Monitor 19073 AIRALERT96D 05/2006 Prelim REVC Copyright © 2006 Honeywell Analytics. All Rights Reserved.