Installation Power-limited Wiring Requirements
24 MS-2/MS-4 PN 51512:E 01/18/05
2.5 Power-limited Wiring RequirementsPower-limited and nonpower-limited circuit wiring must remain separated in the
cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away
from any nonpower-limited circuit wiring. Furthermore, all power-limited and
nonpower-limited circuit wiring must enter and exit the cabinet through different
knockouts and/or conduits. A typical wiring diagram for the MS-4 is illustrated below.