AC Power - TB8
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
Battery (sealed lead acid only) - J8
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the Fire•Lite
Initiating Device Circuits - TB3
Alarm Zones 1 & 2
Alarm Zones 3 & 4
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC, Maximum 27 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA maximum
Maximum Loop Resistance: 100 ohms
Standby Current: 4 mA
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB21
One NAC on
Normal Operating Voltage: Nominal 24 VDC, Maximum 27 VDC
Maximum Signaling Current: 2.5 amps total with standard transformer. 5.0 amps total (2.5 amp maximum per NAC) with optional transformer on
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Form-C Relays
Trouble Relay TB5
Alarm Relay TB6
Supervisory Relay TB7
Relay Contact Ratings: 2 amps @ 30 VAC (resistive)
Resettable Special Application Power - TB1
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Nonresettable Special Application Power - TB1 (MS-4 only)
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
1.Total current for resettable power and one Notification Appliance Circuit must not exceed 3.0 amps for the