Calculating the Battery Size

Power Supply Calculations

5.4Calculating the Battery Size

Use Table 5-4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power. Complete Table 5-4 as follows:

1.Enter the totals from Table 5-3 on page 46, Calculation Columns 2 and 3 where shown

2.Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)

3.Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours

4.Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH)

5.Write the ampere hour requirements on the Protected Premises label located inside the cabinet door

TABLE 5-4:Total Secondary Power Requirements at 24 VDC

Secondary Standby Load

Required Standby Time

 

 

(total from Table 5-3 Calculation

(24 or 60 hours)

 

 

Column 3)

 

 

 

 

 

[

]

X[

]

=

AH

 

 

 

 

Primary Alarm Load

Required Alarm Time

 

 

(total from Table 5-3 Calculation

(for 5 min., enter 0.084,

 

 

Column 2)

 

for 10 min., enter 0.168)

 

 

[

]

X[

]

=

AH

 

 

 

 

 

Sum of Standby and Alarm Ampere Hours

 

=

AH

 

 

 

 

 

Multiply by the Derating Factor

 

 

X 1.2

 

 

 

 

 

Battery Size, Total Ampere Hours Required

 

=

AH

 

 

 

 

 

 

5.4.1 NFPA Battery Requirements

NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm

NFPA 72 Auxiliary and Remote Station require 60 hours of standby followed by 5 minutes in alarm. Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power

5.4.2 Selecting and Locating Batteries

Select batteries that meet or exceed the total ampere hours calculated in Table 5-4 . The control panel can charge batteries in the 7 AH to 18 AH range. The control panel cabi- net is capable of housing batteries up to 7 AH. Batteries larger than 7 AH require the BB-17F or other UL listed external battery cabinet.

MS-2/MS-4 PN 51512:E 01/18/05

47

Page 47
Image 47
Honeywell MS-2 manual Calculating the Battery Size, 4Total Secondary Power Requirements at 24 VDC

MS-2 specifications

The Honeywell MS-2 is a sophisticated control panel designed for fire alarm detection systems. It is renowned for its reliability, efficiency, and advanced features which make it a popular choice among industry professionals. The MS-2 is especially well-suited for small to medium-sized commercial buildings, providing comprehensive fire detection and alarm capabilities.

One of the standout features of the Honeywell MS-2 is its dual-loop architecture. This allows for the connection of two loop circuits, each capable of supporting a wide range of devices such as smoke detectors, heat detectors, and manual pull stations. This flexibility in device connectivity enables tailored solutions based on specific building requirements, ensuring maximum safety and compliance with fire codes.

The MS-2 incorporates a user-friendly graphical interface that simplifies operation and monitoring. This LCD display provides real-time system status updates, which allows users to quickly identify any issues or alarms. Moreover, it features intuitive navigation buttons, making it easy for operators to interact with system functionalities.

In terms of technology, the MS-2 is built upon a robust digital platform that ensures precise detection and response times. With advanced signal processing capabilities, the system can differentiate between actual fire signals and nuisance alarms, thereby minimizing false alarms. This not only enhances safety but also reduces unnecessary disruptions and maintenance costs.

The MS-2 also supports addressable technology, enabling precise identification of device locations within the system. This is particularly beneficial in emergency situations where rapid response is critical. Furthermore, the panel can facilitate remote monitoring, allowing for real-time data access and integration with building management systems, thereby enhancing overall operational efficiency.

Another noteworthy characteristic of the Honeywell MS-2 is its compliance with various industry standards, ensuring that it meets the stringent requirements of fire safety regulations. The system is compatible with a wide range of Honeywell's fire alarm devices, offering versatility and scalability for future expansions.

In conclusion, the Honeywell MS-2 fire alarm control panel combines advanced technology, user-friendly design, and robust features to deliver reliable fire safety solutions. Its dual-loop capability, addressable technology, and real-time monitoring make it an ideal choice for businesses aiming to enhance their fire safety infrastructure. By choosing the MS-2, organizations can better protect their assets, ensure compliance, and safeguard the lives of occupants.