Output Circuits

Installation

2.4.2 Special Application DC Power Output Connections

Resettable 24 VDC special application power is available on both the MS-2 and MS-4 control panels. Nonresettable 24 VDC special application power is available only on the MS-4.

Nonresettable Power (500 mA) - MS-4 Only

4-Wire Smoke Detector Power (500 mA)

24 VDC filtered, nonresettable special

24 VDC filtered, resettable special application power

application power can be obtained from

for 4-wire smoke detectors can be obtained from

these terminals (power-limited)

these terminals (power-limited)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB1

+- + -

Figure 2.7 Special Application Power

ms-4tb1.cdr

2.4.3 Relays

The MS-2 and MS-4 control panels provide an alarm and fail-safe trouble relay and the MS-4 also provides a supervisory relay. Each Form-C relay is rated for 2 amps @ 30VAC (resistive).

Note that relay connections may be power-limited or nonpower-limited, provided that 0.25” minimum spacing is maintained between conductors of power-limited and nonpower-limited circuits.

Note: Relay contacts are shown with power applied to the panel and no active troubles, alarms or supervisories.

The Trouble Relay is a fail-safe relay which will transfer on any trouble or total power failure.

TROUBLE

 

ALARM

 

SUPV

 

 

C TRBL NORM

C

NC NO

C

NC

NO

 

TB5

 

 

TB6

 

TB7

ms4relay.cdr

Figure 2.8 Relay Terminals

MS-2/MS-4 PN 51512:E 01/18/05