Installation Precautions

WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equip- ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.

CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any pro- gramming operation or change in site-specific software. Re- acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software func- tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert- ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de- vices, must also be tested and proper system operation veri- fied.

This system meets NFPA requirements for indoor dry opera- tion at 0-49° C/32-120° F and at a relative humidity of 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the elec- tronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recom- mended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Adherence to the following will aid in problem-free installation with long-term reliability:

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is com- pletely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or out- side aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are antici- pated or encountered.

Disconnect AC power and batteries prior to removing or in- serting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi- cations, verify that they will not interfere with battery, trans- former, and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs.Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re- moved from the body. Use static-suppressive packaging

to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

FCC Warning

WARNING: This equipment generates, uses, and can ra-

Canadian Requirements

diate radio frequency energy and if not installed and used

This digital apparatus does not exceed the Class A

in accordance with the instruction manual, may cause in-

limits for radiation noise emissions from digital

terference to radio communications. It has been tested

apparatus set out in the Radio Interference Regulations

and found to comply with the limits for class A computing

of the Canadian Department of Communications.

device pursuant to Subpart B of Part 15 of FCC Rules,

Le present appareil numerique n'emet pas de bruits

which is designed to provide reasonable protection against

radioelectriques depassant les limites applicables aux

such interference when operated in a commercial environ-

appareils numeriques de la classe A prescrites dans le

ment. Operation of this equipment in a residential area is

Reglement sur le brouillage radioelectrique edicte par le

likely to cause interference, in which case the user will be

ministere des Communications du Canada.

required to correct the interference at his own expense.

 

PrecauLarge.PMD 01/10/2005

Page 3
Image 3
Honeywell MS-2 manual Installation Precautions

MS-2 specifications

The Honeywell MS-2 is a sophisticated control panel designed for fire alarm detection systems. It is renowned for its reliability, efficiency, and advanced features which make it a popular choice among industry professionals. The MS-2 is especially well-suited for small to medium-sized commercial buildings, providing comprehensive fire detection and alarm capabilities.

One of the standout features of the Honeywell MS-2 is its dual-loop architecture. This allows for the connection of two loop circuits, each capable of supporting a wide range of devices such as smoke detectors, heat detectors, and manual pull stations. This flexibility in device connectivity enables tailored solutions based on specific building requirements, ensuring maximum safety and compliance with fire codes.

The MS-2 incorporates a user-friendly graphical interface that simplifies operation and monitoring. This LCD display provides real-time system status updates, which allows users to quickly identify any issues or alarms. Moreover, it features intuitive navigation buttons, making it easy for operators to interact with system functionalities.

In terms of technology, the MS-2 is built upon a robust digital platform that ensures precise detection and response times. With advanced signal processing capabilities, the system can differentiate between actual fire signals and nuisance alarms, thereby minimizing false alarms. This not only enhances safety but also reduces unnecessary disruptions and maintenance costs.

The MS-2 also supports addressable technology, enabling precise identification of device locations within the system. This is particularly beneficial in emergency situations where rapid response is critical. Furthermore, the panel can facilitate remote monitoring, allowing for real-time data access and integration with building management systems, thereby enhancing overall operational efficiency.

Another noteworthy characteristic of the Honeywell MS-2 is its compliance with various industry standards, ensuring that it meets the stringent requirements of fire safety regulations. The system is compatible with a wide range of Honeywell's fire alarm devices, offering versatility and scalability for future expansions.

In conclusion, the Honeywell MS-2 fire alarm control panel combines advanced technology, user-friendly design, and robust features to deliver reliable fire safety solutions. Its dual-loop capability, addressable technology, and real-time monitoring make it an ideal choice for businesses aiming to enhance their fire safety infrastructure. By choosing the MS-2, organizations can better protect their assets, ensure compliance, and safeguard the lives of occupants.