DIP Switch Settings | Program Options via DIP Switch |
Table 3.2 MS-4 DIP Switch Settings
Switch Number | DIP Switch Number | DIP Switch ON |
|
| |
|
|
|
|
| |
| 1 | Silence Inhibit |
|
| |
|
|
|
|
| |
| 2 |
|
| ||
|
|
|
|
| |
| 3 | Temporal Coding |
|
| |
|
|
|
|
| |
| 4 | Selective Silence (if sync. enabled) |
|
| |
SW1 |
|
|
|
| |
5 | Trouble Reminder |
|
| ||
|
|
| |||
|
|
|
|
| |
| 6 | AC Trouble Delay |
|
| |
|
|
|
|
| |
| 7 | Autoresettable Supervisory |
|
| |
|
|
|
|
| |
| 8 | IDC Combination Waterflow/ |
|
| |
|
| Supervisory Circuit |
|
| |
|
|
|
|
| |
| 1 | IDC1 Verification |
|
| |
|
|
|
|
| |
| 2 | IDC1 Supervisory |
|
| |
|
|
|
|
| |
| 3 | IDC2 Verification |
|
| |
|
|
|
|
| |
SW2 | 4 | IDC2 Supervisory |
|
| |
|
|
|
| ||
5 | IDC3 Verification |
|
| ||
|
|
| |||
|
|
|
|
| |
| 6 | IDC3 Supervisory |
|
| |
|
|
|
|
| |
| 7 | IDC4 Verification |
|
| |
|
|
|
|
| |
| 8 | IDC4 Supervisory |
|
| |
|
|
|
|
| |
| 1 | NAC1 Nonsilenceable |
|
| |
|
|
|
|
| |
| 2 | NAC1 Disable |
|
| |
|
|
|
|
| |
| 3 | NAC2 Nonsilenceable |
|
| |
|
|
|
|
| |
| 4 | NAC2 Disable |
|
| |
|
|
|
|
| |
|
|
| Switch 5 | Switch 6 | |
SW3 | 5 & 6 | No Synchronization | OFF | OFF | |
used to select strobe |
|
|
| ||
System Sensor Synchronization | ON | OFF | |||
| synchronization feature as | ||||
|
|
|
| ||
| shown to the right | Gentex Synchronization | OFF | ON | |
|
|
|
|
| |
|
| Wheelock Synchronization | ON | ON | |
|
|
|
|
| |
| 7 | Nonsilenceable Waterflow for |
|
| |
|
| Combination Circuit |
|
| |
|
| (only if SW1 switch 8 is ON) |
|
| |
|
|
|
|
| |
| 8 | spare |
|
| |
|
|
|
|
|
33 |