Press and release the Power On/Standby button.

This method initiates a controlled shutdown of applications and the OS before the server blade enters standby mode.

Press and hold the Power On/Standby button for more than 4 seconds to force the server blade to shut down.

This method forces the server blade to enter standby mode without properly exiting applications and the OS. It provides an emergency shutdown method in the event of a hung application.

IMPORTANT: When the server blade is in standby mode, auxiliary power is still being provided. To remove all power from the server blade, remove the server blade from the enclosure.

After initiating a virtual power down command, be sure that the server blade goes into standby mode by observing that the system power LED is amber.

Power down the enclosure

1.Power down the server blades ("Power down the server blade" on page 29).

2.Disconnect all AC power cables.

HP BladeSystem c7000 power supply or power supply blank

To remove the component:

CAUTION: This procedure provides instructions for replacement of a failed part only. To change the configuration of components, see the appropriate HP BladeSystem c-Class enclosure setup and installation guide.

NOTE: To access all power supply bays, slide the HP BladeSystem Insight Display to the right or left.

1.Press the release button.

2.Pull down the handle.

Removal and replacement procedures 30