QuickSpecs

HP ProLiant DL160 Generation 5

Standard Features

Server Power Cords

One 6' Highline (IEC-IEC) power cord ships standard

 

NOTE: HP ProLiant DL servers no longer ship standard with NEMA power cords (163719-002)

 

that allow connection to 110V US wall outlets in a home or office. ProLiant DL servers are

 

primarily connected to PDU's in data center racks so they now ship standard with only a PDU

 

power cord (416151-B21). If a user wishes to power a ProLiant DL server using a 110V receptacle

 

(NEMA-15), the NEMA power cord (227099-001) must be ordered separately.

 

If customers require a local power cord, they can check the power cord matrix for the appropriate

 

cord. Please see the following power cord matrix: http://www.hp.com/go/powercordmatrix.

 

 

 

UPS and PDU Power

Please see the UPS and PDU cable matrix that lists cable descriptions, requirements, and

Cord Matrix

specifications for UPS and PDU units:

 

http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/index.html.

 

 

 

Power Supply

650 Watts, auto-switching, PFC (Power Factor Correcting)

 

NOTE: Factory upgradeable to high-efficiency (HE) power supply for lower TCO

 

 

 

System Fans

6 system fans ship standard; Non-hot plug, Non-redundant

 

 

 

OS Support

Microsoft Windows Server 2003 R2

 

Microsoft Windows Server 2008

 

Microsoft Windows Small Business Server 2008

 

Microsoft Windows Essential Server 2008

 

Red Hat Enterprise Linux

 

SUSE Linux Enterprise Server

 

Sun Solaris for x64/x86-based Systems

 

NOTE: For more information on HP's Certified and Supported ProLiant Servers for OS and

 

Virtualization Software and latest listing of software drivers available for your server, please visit

 

our Support Matrix at: http://www.hp.com/go/supportos and our driver download page

 

http://www.hp.com/support/DL160G5.

 

 

 

Rack Airflow

Rack 10000 series Cabinets

Requirements

The increasing power of new high-performance processor technology requires increased cooling

 

efficiency for rack-mounted servers. The 10000 Series Racks provide enhanced airflow for

 

maximum cooling, allowing these racks to be fully loaded with servers using the latest processors.

 

CAUTION: If a third-party rack is used, observe the following additional requirements to ensure

 

adequate airflow and to prevent damage to the equipment:

 

Front and rear doors: If your 42U server rack includes closing front and rear doors, you must allow

 

5,350 sq cm (830 square inches) of hole evenly distributed from top to bottom to permit adequate

 

airflow (equivalent to the required 64 percent open area for ventilation).

 

Side: The clearance between the installed rack component and the side panels of the rack must

 

be a minimum of 7 cm (2.75 inches)

 

CAUTION: Always use blanking panels to fill all remaining empty front panel U-spaces in the rack.

 

This arrangement ensures proper airflow. Using a rack without blanking panels results in improper

 

cooling that can lead to thermal damage.

DA - 12902 Worldwide QuickSpecs — Version 19 — 1/26/2009

Page 9

Page 9
Image 9