Parameter | Range |
|
|
Calcium hardness (CaCO3) | |
Magnesium hardness (CaCO3) | |
Copper (Cu) | < 0.20 ppm |
Iron (Fe) | < 3.0 ppm |
Aluminum (Al) | < 0.50 ppm |
Sodium (Na) | |
Silica (SiO2) | |
Zinc (Zn) | < 1.0 ppm |
Manganese (Mn) | < 0.1 ppm |
Phosphate Ortho- (PO4) | < 3 ppm |
Bacteria | < 1000 CFU/ml |
Suspended solids | < 10 ppm |
If your water is out of range, consult a water quality expert.
The following table describes the chilled water system specifications for the HP POD 20c.
Feature | Specification |
|
|
Facility input temperature to the HP POD | 12º to 24ºC (55º to 75ºF) |
20c |
|
Max design pressure | 1,034 kPa (150 psi) |
HP POD 20c pressure drop | 172.4 kPa (25 psi) |
HP POD 20c water flow rate | 454 lpm (120 gpm*) |
Chilled water supply and return | Two DIN PN16 DN80 flanges |
connections |
|
Piping materials
Do not use the following interconnecting piping materials in a closed water system:
•Oxidizing biocides
•Aluminum components
•Brass components with high levels of zinc
•
•PVC
IMPORTANT: Even though some PVC grade piping materials are designed to handle the expected water pressure, the use of PVC materials should be reviewed and approved by the customer site engineers.
Power infrastructure installation
When determining the final location of the power connections, consider the following:
•Distance between the facility utilities and the location of the HP POD 20c