HP POD 20c access control
The HP POD 20c is equipped with standard key lock hardware for each personnel entry door and external electrical cabinet. Each personnel entry door includes a door access contact that can be connected to the customer facility security system.
Additional options for controlled access include the following:
•Electronic card reader
•
•Magnetic lock on each personnel access door and dynamic hot aisle door
Fire, safety, and access notifications
Dry contacts are provided to enable the connection between the HP POD 20c and the customer’s facility. If the HP POD 20c is connected to the customer facility systems, then the alarm conditions of the HP POD 20c can be detected by the facility systems.
It is your responsibility to facilitate these connections. HP can make these connections when specifically contracted to deliver these services and a Scope of Work has been drafted, reviewed, and signed for delivery services.
The customer must provide an independent connection for each system listed in the following table.
Alarm | Description |
|
|
Fire prevention alarm | Smoke is detected in the HP POD 20c. |
Fire suppression | The suppression system alarm is activated and gas is |
system (optional) | dispersed to suppress a fire. |
Access control | A door of the POD has been opened. |
EPO | The EPO system is activated by manually pressing the |
| EPO button or by a thermal event, and the HP POD 20c |
| is shut down. |
|
|
The electrical layout of the fire alarm system is described in the schematic drawing that is supplied with the HP Performance Optimized Datacenter 20c Site Drawing Package.
Fire box
The communication connections between the fire system and the HP POD 20c are made through the fire box.
Supported facility connections 18