•Do not treat the water with softeners. Softeners can produce foam, which affects the operation of the unit.
•Do not use well water, industrial water, water from cooling circuits, or water contaminated by any chemicals or bacteria.
•Do not add potential irritants to the water, such as disinfectants or
•The manufacturer recommends installing an
For more information, see the Operations and Maintenance Manual or the HP Performance Optimized Datacenter 20c Maintenance and Service Guide.
Drainage
Requirement | Location | Specification |
|
|
|
Condensate drains | Hot aisle side (2) | 3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max |
Chill Water Header drains | Cold aisle side (2) | 3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max |
Humidifier drain | Cold aisle side (1) | 3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max |
Chilled water supply
The following are the water quality requirements and specifications:
•
•The temperature of the chilled water supplied to the HP POD 20c must be 12ºC to 24ºC (55ºF to 75ºF).
CAUTION: Freezing water can cause a blockage and damage to the unit. In outside locations that are subject to freezing temperatures, an additive such as glycol might be necessary to lower the freezing point. However, since the heat transfer potential of water with glycol is lower, the HP POD 20c must be
IMPORTANT: The chilled water system piping and heat exchangers must be drained completely, and then purged using compressed air when storing or transporting at or below freezing temperatures.
IMPORTANT: Operating the chilled water system at the higher end of the acceptable range decreases the overall thermal capacity of the POD.
Acceptable water quality specifications
Water must be maintained per the following acceptable water quality standards.
Parameter | Range |
|
|
pH | |
Specific conductance at 25ºC (77ºF) | |
Alkalinity ("M" as CaCO3) | |
Sulfur (SO4) | |
Chloride (Cl) | |
Hardness (CaCO3) |